Equipment grounding conductors
NEC Table 250.122 minimum copper and aluminum EGC sizes by overcurrent device rating. Click any row to open that wire size in the wire size calculator.
Table 250.122 minimum EGC sizes
| Max OCPD rating (A) |
Copper EGC size |
Copper area | Aluminum / CCA EGC size |
Aluminum area | Open in calculator |
|---|
No rows match that filter. Try a breaker rating like “100” or an EGC size like “8”.
Rules for sizing equipment grounding conductors
Proportional upsizing (NEC 250.122(B)): When ungrounded phase conductors are increased in size for voltage drop or other reasons, the equipment grounding conductor must be increased proportionally in circular mil area by the same ratio as the installed phase conductor to the minimum code-sized phase conductor.
Not larger than circuit conductors (NEC 250.122(A)): An equipment grounding conductor is never required to be larger than the circuit conductors supplying the equipment.
Parallel runs (NEC 250.122(F)): When conductors are run in parallel in multiple raceways or cables, a full-sized EGC based on the total overcurrent device rating must be installed in each raceway or cable.