Wirebench
AWG, ft, °Fmm², m, °C

Wire and cable size calculator

Recommended copper and aluminum conductor sizes checked against NEC 310.16 ampacity, 110.14(C) terminals, 240.4(D) limits, and voltage drop.

Circuit parameters

A
V
ft
Phase
Duty cycle (NEC 210.19 / 215.2)
Insulation rating
Terminal rating (NEC 110.14(C))
°F
%
CCC
Recommended conductor sizes No result
Copper (Cu) —
—
Enter load and distance
Aluminum (Al) —
—
Enter load and distance

Enter load, voltage and distance to size copper and aluminum conductors.

Design ampacity req.
—
Copper drop
—
Aluminum drop
—
Next std breaker (240.6)
—
Cu EGC (250.122)
—
Al EGC (250.122)
—

Materials take-off

Line item Copper option Aluminum option Qty / Length

IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance at 20 °C adjusted to 75 °C for voltage drop.

Advertisement

How NEC wire sizing balances ampacity and voltage drop

Selecting an electrical conductor requires satisfying two independent constraints simultaneously: thermal ampacity under NEC Article 310 and voltage drop performance under NEC 210.19(A) and 215.2(A). The larger wire gauge required by either criterion governs the final installation.

I_required = I_load × (1.25 if continuous else 1.00) Size_ampacity: smallest gauge where min(I_adjusted, I_terminal) ≥ I_required and I_required ≤ OCPD_240.4(D) Size_drop: smallest gauge where %VD = (K × I_load × R × L / 1000) / V_system × 100 ≤ Max_VD%

Ampacity and continuous loads: Under NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders, conductors supplying continuous loads (running 3 hours or more) must have an allowable ampacity not less than 125% of the continuous load before applying terminal limits. Ambient temperatures above 30 °C (86 °F) or more than three current-carrying conductors in a raceway require derating from the insulation column using NEC 310.15(B) and (C).

Voltage drop and EGC upsizing (NEC 250.122(B)): Although NEC informational notes recommend keeping branch-circuit drop within 3% and combined feeder-plus-branch drop within 5%, voltage drop calculations use the actual load current (not the 125% continuous multiplier). Whenever you increase ungrounded conductors above the code-minimum ampacity size to meet voltage drop, NEC 250.122(B) requires increasing the equipment grounding conductor proportionally by circular mil area.

Three worked wire sizing examples

Example 1: 40 A continuous EV charger at 240 V, 75 ft (Ampacity governs)

A Level 2 EVSE draws 40 A continuous at 240 V single-phase over a 75 ft one-way run in 30 °C ambient with three conductors in EMT, 90 °C THHN on 75 °C breakers, and a 3% drop limit.

Design current = 40 A × 1.25 = 50 A Copper ampacity check: 8 AWG Cu = 50 A at 75 °C terminals (satisfies 50 A) Copper voltage drop: 2 × 40 × 0.778 × 0.075 / 240 = 1.95% (≤ 3%) Aluminum ampacity check: 6 AWG Al = 50 A at 75 °C terminals (2.02% drop)

Both copper (8 AWG) and aluminum (6 AWG) meet the 3% voltage drop budget with margin to spare, so thermal ampacity governs the conductor selection on this 50 A circuit.

Example 2: 40 A non-continuous shop circuit at 240 V, 250 ft (Voltage drop governs)

The same 40 A load is now non-continuous (100% duty) and located 250 ft away in an outbuilding, with a 3% maximum voltage drop.

Ampacity minimum: 8 AWG Cu (50 A at 75 °C) or 8 AWG Al (40 A at 75 °C) Voltage drop at 8 AWG Cu: 2 × 40 × 0.778 × 0.250 / 240 = 6.48% (exceeds 3%) 4 AWG Cu drop: 2 × 40 × 0.308 × 0.250 / 240 = 2.57% (≤ 3%) 2 AWG Al drop: 2 × 40 × 0.319 × 0.250 / 240 = 2.66% (≤ 3%)

Distance forces a jump of two trade sizes in copper (from 8 AWG to 4 AWG) and three sizes in aluminum (from 8 AWG to 2 AWG). Because the phase conductors were upsized for voltage drop, NEC 250.122(B) also scales the 10 AWG copper EGC up to 4 AWG copper (26,242 cmil required > 26,240 cmil of 6 AWG).

Example 3: 100 A continuous 480 V 3-phase feeder in 40 °C, 6 CCC, 300 ft

A 480 V 3-phase continuous feeder carries 100 A for 300 ft in a 40 °C factory truss with six current-carrying 90 °C conductors in raceway and 75 °C equipment lugs.

Design current = 100 A × 1.25 = 125 A Derating factors: 0.91 (40 °C) × 0.80 (6 CCC) = 0.728 1/0 Cu adjusted = 170 × 0.728 = 123.8 A (short of 125 A) 2/0 Cu adjusted = 195 × 0.728 = 142.0 A ≥ 125 A (75 °C terminal = 175 A) 2/0 Cu voltage drop = √3 × 100 × 0.0967 × 0.300 / 480 = 1.05%

Ambient derating and bundling govern at 2/0 AWG copper, whereas 480 V 3-phase keeps voltage drop to just 1.05% across 300 ft.

Frequently asked questions

When does voltage drop govern wire size instead of ampacity? Voltage drop governs on long runs or low-voltage systems (12 V, 24 V, 120 V) where cable resistance causes more than 3% or 5% drop even though a smaller gauge could safely carry the thermal current.
When should I enable the 125% continuous load toggle? Enable 125% for loads expected to operate at maximum current for three hours or longer (EV chargers, commercial lighting, electric space/water heating) per NEC 210.19(A)(1) and 215.2(A)(1).
Do I also need to upsize the equipment grounding conductor when I upsize for voltage drop? Yes. NEC 250.122(B) requires increasing the EGC circular mil area in the same proportion that the ungrounded circuit conductors were increased above the minimum ampacity size.