Wire and cable size calculator
Recommended copper and aluminum conductor sizes checked against NEC 310.16 ampacity, 110.14(C) terminals, 240.4(D) limits, and voltage drop.
Circuit parameters
Enter load, voltage and distance to size copper and aluminum conductors.
- Design ampacity req.
- —
- Copper drop
- —
- Aluminum drop
- —
- Next std breaker (240.6)
- —
- Cu EGC (250.122)
- —
- Al EGC (250.122)
- —
Materials take-off
| Line item | Copper option | Aluminum option | Qty / Length |
|---|
IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance at 20 °C adjusted to 75 °C for voltage drop.
How NEC wire sizing balances ampacity and voltage drop
Selecting an electrical conductor requires satisfying two independent constraints simultaneously: thermal ampacity under NEC Article 310 and voltage drop performance under NEC 210.19(A) and 215.2(A). The larger wire gauge required by either criterion governs the final installation.
I_required = I_load × (1.25 if continuous else 1.00)
Size_ampacity: smallest gauge where min(I_adjusted, I_terminal) ≥ I_required and I_required ≤ OCPD_240.4(D)
Size_drop: smallest gauge where %VD = (K × I_load × R × L / 1000) / V_system × 100 ≤ Max_VD%
Ampacity and continuous loads: Under NEC 210.19(A)(1) for branch circuits and 215.2(A)(1) for feeders, conductors supplying continuous loads (running 3 hours or more) must have an allowable ampacity not less than 125% of the continuous load before applying terminal limits. Ambient temperatures above 30 °C (86 °F) or more than three current-carrying conductors in a raceway require derating from the insulation column using NEC 310.15(B) and (C).
Three worked wire sizing examples
Example 1: 40 A continuous EV charger at 240 V, 75 ft (Ampacity governs)
A Level 2 EVSE draws 40 A continuous at 240 V single-phase over a 75 ft one-way run in 30 °C ambient with three conductors in EMT, 90 °C THHN on 75 °C breakers, and a 3% drop limit.
Design current = 40 A × 1.25 = 50 A
Copper ampacity check: 8 AWG Cu = 50 A at 75 °C terminals (satisfies 50 A)
Copper voltage drop: 2 × 40 × 0.778 × 0.075 / 240 = 1.95% (≤ 3%)
Aluminum ampacity check: 6 AWG Al = 50 A at 75 °C terminals (2.02% drop)
Both copper (8 AWG) and aluminum (6 AWG) meet the 3% voltage drop budget with margin to spare, so thermal ampacity governs the conductor selection on this 50 A circuit.
Example 2: 40 A non-continuous shop circuit at 240 V, 250 ft (Voltage drop governs)
The same 40 A load is now non-continuous (100% duty) and located 250 ft away in an outbuilding, with a 3% maximum voltage drop.
Ampacity minimum: 8 AWG Cu (50 A at 75 °C) or 8 AWG Al (40 A at 75 °C)
Voltage drop at 8 AWG Cu: 2 × 40 × 0.778 × 0.250 / 240 = 6.48% (exceeds 3%)
4 AWG Cu drop: 2 × 40 × 0.308 × 0.250 / 240 = 2.57% (≤ 3%)
2 AWG Al drop: 2 × 40 × 0.319 × 0.250 / 240 = 2.66% (≤ 3%)
Distance forces a jump of two trade sizes in copper (from 8 AWG to 4 AWG) and three sizes in aluminum (from 8 AWG to 2 AWG). Because the phase conductors were upsized for voltage drop, NEC 250.122(B) also scales the 10 AWG copper EGC up to 4 AWG copper (26,242 cmil required > 26,240 cmil of 6 AWG).
Example 3: 100 A continuous 480 V 3-phase feeder in 40 °C, 6 CCC, 300 ft
A 480 V 3-phase continuous feeder carries 100 A for 300 ft in a 40 °C factory truss with six current-carrying 90 °C conductors in raceway and 75 °C equipment lugs.
Design current = 100 A × 1.25 = 125 A
Derating factors: 0.91 (40 °C) × 0.80 (6 CCC) = 0.728
1/0 Cu adjusted = 170 × 0.728 = 123.8 A (short of 125 A)
2/0 Cu adjusted = 195 × 0.728 = 142.0 A ≥ 125 A (75 °C terminal = 175 A)
2/0 Cu voltage drop = √3 × 100 × 0.0967 × 0.300 / 480 = 1.05%
Ambient derating and bundling govern at 2/0 AWG copper, whereas 480 V 3-phase keeps voltage drop to just 1.05% across 300 ft.