AWG, ft, °Fmm², m, °C

AWG / kcmil ↔ Metric mm² converter

Instant bidirectional lookup between AWG, kcmil, and IEC 60228 mm² with circular mils, diameter, resistance, and conservative NEC ampacity.

Conductor lookup

Lookup direction
Select any AWG or kcmil gauge to convert to metric mm².
Select any IEC 60228 size to find nearest and conservative AWG.
mm²
Conductor material
Metric mm² equivalent No result
— mm²

Select an AWG, IEC mm², or custom area to convert.

Cross-section (mm²)
—
Circular mils (cmil)
—
Bare diameter (mm / in)
—
DC R @ 75 °C (Ω/kft | Ω/km)
—
DC R @ 20 °C (Ω/kft | Ω/km)
—
NEC 310.16 (60 / 75 / 90 °C)
—

Standard AWG / kcmil and IEC 60228 cross-reference

24 rows
—

Conservative NEC mapping: When looking up an IEC mm² conductor in NEC tables, ampacity uses the largest AWG or kcmil gauge whose area does not exceed the metric cross-section (within a 0.5% tolerance) so NEC ampacity is never overstated.

Advertisement

AWG, circular mils, and IEC 60228 conversion formulas

North American wire gauges follow the American Wire Gauge (AWG) logarithmic system through 4/0 AWG and circular mils (kcmil) from 250 through 1000 kcmil, whereas international IEC 60228 conductors are specified by nominal cross-sectional area in square millimeters (mm²).

Circular mils to mm²: Area_mm2 = cmil × 5.067075 × 10^-4 (1 kcmil = 0.5067 mm²) mm² to circular mils: cmil = Area_mm2 / 5.067075 × 10^-4 Equivalent bare dia.: d_mm = 2 × √(Area_mm2 / π) | d_in = d_mm / 25.4 = √(cmil) / 1000 Resistance conversion: Ω/km = Ω/1000 ft / 0.3048 | Ω/1000 ft = Ω/km × 0.3048
Standard sizes rarely match exactly: Because AWG progresses geometrically by a factor of ~1.261 per gauge step while IEC 60228 follows preferred metric numbers (1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 mm²...), the closest nominal size may be slightly smaller or larger. Always check whether the nearest size is a downsize or upsize before substituting across NEC and IEC specifications.

Three worked AWG and metric conversion examples

Example 1: Converting 12 AWG copper to metric mm²

NEC Chapter 9 Table 8 lists 12 AWG at 6,530 cmil and 1.98 Ω/1000 ft DC resistance at 75 °C.

Area = 6,530 × 0.0005067075 = 3.31 mm² (nearest IEC: 4 mm², +20.9% larger) Bare solid diameter = 2 × √(3.31 / π) = 2.053 mm (0.0808 in) DC resistance = 1.98 / 0.3048 = 6.50 Ω/km at 75 °C | 75 °C Cu ampacity = 25 A

Because IEC has no 3.3 mm² standard step between 2.5 and 4 mm², 4 mm² is the nearest and next-larger metric equivalent.

Example 2: Converting 50 mm² IEC cable to AWG (nearest vs. conservative NEC)

An IEC 60228 50 mm² copper conductor has a maximum 20 °C resistance of 0.387 Ω/km (0.471 Ω/km or 0.143 Ω/1000 ft adjusted to 75 °C).

Circular mils = 50 / 0.0005067075 = 98,676 cmil Nearest AWG by area: 1/0 AWG (105,600 cmil = 53.51 mm², +7.0% larger) Conservative NEC AWG: 1 AWG (83,690 cmil = 42.41 mm², 130 A Cu @ 75 °C)

Although 50 mm² is closest in size to 1/0 AWG, it has 6.6% less copper than 1/0 AWG. Conservative NEC ampacity lookup therefore uses 1 AWG (130 A at 75 °C) instead of 1/0 AWG (150 A).

Example 3: Converting 250 kcmil feeder to circular mils and mm²

A 250 kcmil conductor equals 250,000 cmil by definition.

Area = 250,000 × 0.0005067075 = 126.68 mm² (nearest IEC: 120 mm², next-larger: 150 mm²) Bare solid diameter = √(250,000) / 1000 = 0.5000 in (12.70 mm) 75 °C DC resistance = 0.0515 Ω/kft (0.169 Ω/km) | 75 °C Cu ampacity = 255 A

When exporting equipment wired for 250 kcmil to an IEC project, 120 mm² is closest in area (-5.3%), while 150 mm² guarantees full cross-sectional parity (+18.4%).

Frequently asked questions

How do I convert AWG or kcmil to square millimeters (mm²)? Multiply circular mils from NEC Chapter 9 Table 8 by 0.0005067075. For kcmil sizes, multiply kcmil by 0.5067075.
What is a conservative NEC ampacity equivalent for an IEC metric wire? It is the NEC Table 310.16 ampacity of the largest AWG or kcmil size whose area is less than or equal to the metric conductor's mm² (within 0.5%), ensuring ampacity is never overstated.
Why is the bare conductor diameter smaller than the insulated wire diameter? Bare equivalent solid diameter reflects pure metal cross-sectional area, whereas stranded conductors include inter-strand gaps and THHN/XHHW insulation adds jacket thickness (listed in NEC Chapter 9 Table 5).