AWG / kcmil ↔ Metric mm² converter
Instant bidirectional lookup between AWG, kcmil, and IEC 60228 mm² with circular mils, diameter, resistance, and conservative NEC ampacity.
Conductor lookup
Select an AWG, IEC mm², or custom area to convert.
- Cross-section (mm²)
- —
- Circular mils (cmil)
- —
- Bare diameter (mm / in)
- —
- DC R @ 75 °C (Ω/kft | Ω/km)
- —
- DC R @ 20 °C (Ω/kft | Ω/km)
- —
- NEC 310.16 (60 / 75 / 90 °C)
- —
Standard AWG / kcmil and IEC 60228 cross-reference
—
Conservative NEC mapping: When looking up an IEC mm² conductor in NEC tables, ampacity uses the largest AWG or kcmil gauge whose area does not exceed the metric cross-section (within a 0.5% tolerance) so NEC ampacity is never overstated.
AWG, circular mils, and IEC 60228 conversion formulas
North American wire gauges follow the American Wire Gauge (AWG) logarithmic system through 4/0 AWG and circular mils (kcmil) from 250 through 1000 kcmil, whereas international IEC 60228 conductors are specified by nominal cross-sectional area in square millimeters (mm²).
Circular mils to mm²: Area_mm2 = cmil × 5.067075 × 10^-4 (1 kcmil = 0.5067 mm²)
mm² to circular mils: cmil = Area_mm2 / 5.067075 × 10^-4
Equivalent bare dia.: d_mm = 2 × √(Area_mm2 / π) | d_in = d_mm / 25.4 = √(cmil) / 1000
Resistance conversion: Ω/km = Ω/1000 ft / 0.3048 | Ω/1000 ft = Ω/km × 0.3048
Three worked AWG and metric conversion examples
Example 1: Converting 12 AWG copper to metric mm²
NEC Chapter 9 Table 8 lists 12 AWG at 6,530 cmil and 1.98 Ω/1000 ft DC resistance at 75 °C.
Area = 6,530 × 0.0005067075 = 3.31 mm² (nearest IEC: 4 mm², +20.9% larger)
Bare solid diameter = 2 × √(3.31 / π) = 2.053 mm (0.0808 in)
DC resistance = 1.98 / 0.3048 = 6.50 Ω/km at 75 °C | 75 °C Cu ampacity = 25 A
Because IEC has no 3.3 mm² standard step between 2.5 and 4 mm², 4 mm² is the nearest and next-larger metric equivalent.
Example 2: Converting 50 mm² IEC cable to AWG (nearest vs. conservative NEC)
An IEC 60228 50 mm² copper conductor has a maximum 20 °C resistance of 0.387 Ω/km (0.471 Ω/km or 0.143 Ω/1000 ft adjusted to 75 °C).
Circular mils = 50 / 0.0005067075 = 98,676 cmil
Nearest AWG by area: 1/0 AWG (105,600 cmil = 53.51 mm², +7.0% larger)
Conservative NEC AWG: 1 AWG (83,690 cmil = 42.41 mm², 130 A Cu @ 75 °C)
Although 50 mm² is closest in size to 1/0 AWG, it has 6.6% less copper than 1/0 AWG. Conservative NEC ampacity lookup therefore uses 1 AWG (130 A at 75 °C) instead of 1/0 AWG (150 A).
Example 3: Converting 250 kcmil feeder to circular mils and mm²
A 250 kcmil conductor equals 250,000 cmil by definition.
Area = 250,000 × 0.0005067075 = 126.68 mm² (nearest IEC: 120 mm², next-larger: 150 mm²)
Bare solid diameter = √(250,000) / 1000 = 0.5000 in (12.70 mm)
75 °C DC resistance = 0.0515 Ω/kft (0.169 Ω/km) | 75 °C Cu ampacity = 255 A
When exporting equipment wired for 250 kcmil to an IEC project, 120 mm² is closest in area (-5.3%), while 150 mm² guarantees full cross-sectional parity (+18.4%).