Wire resistance, reactance and power loss

DC resistance, AC effective resistance, inductive reactance in PVC vs. steel conduit, circuit impedance, and annual energy cost from NEC Chapter 9 Tables 8 and 9.

Conductor and load parameters

Conductor material
Phase
Conduit / impedance model
NEC Chapter 9 Table 9 in PVC conduit at 60 Hz.
ft
°F
75.0 °C (Table 8 & 9 base)
A
PF
Lagging PF (0.85)
hr/yr
$/kWh
V
Conductor power loss and impedance No result
— W

Enter wire size, run length, and load current to calculate resistance and loss.

DC resistance (Table 8)
—
AC resistance (Table 9)
—
Inductive reactance XL
—
Impedance |Z| / Z_eff
—
Annual energy loss
—
Annual energy cost
—

PVC vs. aluminum vs. steel conduit comparison

Click any row to switch the active impedance model. Values include temperature correction and parallel sets.

Model / Conduit R (Ω/kft) XL (Ω/kft) |Z| (Ω/kft) Z_eff (Ω/kft) Run R (Ω) Loss (W) Energy (kWh/yr) Cost ($/yr)
—

In IEC mode, Table 8 DC calculations use IEC 60228 class 2 maximum resistance adjusted from 20 °C; Table 9 inductive reactance uses the nearest AWG conduit reactance.

Advertisement

Resistance, reactance, impedance, and power loss formulas

NEC Chapter 9 Table 8 provides conductor DC resistance at 75 °C, while Table 9 provides 60 Hz AC resistance (R_ac) and inductive reactance (X_L) for three single conductors in PVC, aluminum, and steel conduit. Temperature adjustment follows Chapter 9 Table 8 Note 2.

Temperature adjusted R: R_T = R_75 × [1 + α × (T − 75)] (α_Cu = 0.00323/°C, α_Al = 0.00330/°C) Impedance magnitude: |Z| = √(R_ac² + X_L²) Effective impedance: Z_eff = R_ac × PF + X_L × sin(arccos(PF)) Real power loss (W): P_loss = N_cond × I² × R_run (N_cond = 3 for 3-phase, 2 for 1-phase/DC) Annual energy & cost: kWh/yr = (P_loss / 1000) × hours/yr | Cost = kWh/yr × $/kWh
Steel vs. PVC conduit: Ferromagnetic steel conduit concentrates alternating magnetic flux around the conductors, raising inductive reactance X_L by roughly 25% and introducing eddy-current losses that raise R_ac in larger copper and aluminum feeders. Note that real heat loss in Watts depends on R_ac, whereas X_L increases reactive voltage drop (Z_eff).

Three worked wire resistance and energy loss examples

Example 1: 250 kcmil copper 200 A feeder at 250 ft, PVC vs. steel conduit

A 480 V 3-phase 200 A continuous industrial feeder runs 250 ft one-way at 75 °C and 0.85 power factor on 250 kcmil copper (operating 4,000 hr/yr at $0.15/kWh).

PVC conduit (Table 9): R_ac = 0.052 Ω/kft, X_L = 0.041 Ω/kft, Z_eff = 0.0658 Ω/kft P_loss = 3 × 200² × (0.052 × 0.25) = 1,560 W (6,240 kWh/yr = $936/yr) Steel conduit (Table 9): R_ac = 0.054 Ω/kft, X_L = 0.052 Ω/kft, Z_eff = 0.0733 Ω/kft P_loss = 3 × 200² × (0.054 × 0.25) = 1,620 W (6,480 kWh/yr = $972/yr)

Switching from PVC to steel conduit raises effective voltage-drop impedance by 11.4% and adds 60 W of continuous eddy-current heat dissipation in the raceway.

Example 2: 12 AWG copper 20 A single-phase branch at 100 ft

A 120 V single-phase 20 A branch circuit runs 100 ft one-way (200 ft loop) on 12 AWG copper at 75 °C (R_dc = 1.98 Ω/kft, Table 9 R_ac = 2.0 Ω/kft).

Run DC resistance (1-way) = 1.98 × (100 / 1000) = 0.198 Ω Loop DC resistance (2-wire) = 2 × 0.198 = 0.396 Ω P_loss = 2 × 20² × 0.198 = 158.4 W (at 2,000 hr/yr: 316.8 kWh/yr = $47.52/yr)

At 12 AWG, skin effect is negligible, so Table 8 DC resistance and Table 9 AC resistance match within 1%.

Example 3: Temperature correction on 4/0 AWG aluminum at 90 °C

A 4/0 AWG aluminum feeder in PVC conduit operates near its 90 °C thermal limit (base Table 9 R_ac75 = 0.10 Ω/kft, X_L = 0.041 Ω/kft) at 0.90 power factor.

R_ac(90 °C) = 0.10 × [1 + 0.00330 × (90 − 75)] = 0.1050 Ω/kft (+5.0%) |Z| = √(0.1050² + 0.041²) = 0.1127 Ω/kft Z_eff = 0.1050 × 0.90 + 0.041 × sin(arccos(0.90)) = 0.1123 Ω/kft

Inductive reactance X_L stays constant with temperature because geometry does not change, while resistive heating R_ac increases by 5.0% from 75 °C to 90 °C.

Frequently asked questions

Why is AC resistance higher than DC resistance on larger wire gauges? Skin effect pushes 60 Hz alternating current toward the conductor perimeter, and proximity effect plus magnetic steel conduit eddy currents increase effective AC resistance on 1/0 AWG and larger conductors.
Does inductive reactance X_L increase real power loss in Watts and kWh? No. Real energy lost as heat (Watts and kWh/yr) comes only from conductor resistance R. Inductive reactance X_L creates reactive voltage drop (included in Z_eff and |Z|) without dissipating real power.
How does conductor temperature affect wire resistance and energy loss? Resistance rises linearly with temperature using α = 0.00323/°C for copper and 0.00330/°C for aluminum at 75 °C. Running a conductor cooler or upsizing one gauge lowers both resistance and annual energy cost.

Related calculators and reference charts

Conductor power loss —
No result View