Maximum wire run length calculator

Longest one-way conductor run in feetmeters before exceeding 2%, 3%, or 5% voltage drop, plus all standard gauges side by side.

Circuit parameters

Phase
V
A
Voltage drop limit
Conductor material
Impedance model / conduit
Chapter 9 Table 8 DC resistance at 75 °C.
PF
Unity (1.00) resistive
Maximum one-way run length No result
— ft

Enter voltage, load current, and wire size to compute maximum distance.

Max run at 2% drop
—
Max run at 3% drop
—
Max run at 5% drop
—
Allowable volts lost
—
75 °C wire ampacity
—
Effective R / Z_eff
—

Max distance across all standard gauges

Click any row to select that gauge above. Highlighted row is the active selection.

Gauge 75 °C (A) DC R (Ω/kft) Max @ 2% Max @ 3% Max @ 5% Ampacity check
—

In IEC mode, Table 8 DC calculations use IEC 60228 resistance adjusted from 20 °C to 75 °C; NEC 75 °C ampacity uses the conservative AWG size that does not exceed the metric cross-section.

Advertisement

Maximum run length formula and NEC considerations

When laying out a feeder, outbuilding subpanel, EV charger, or remote pump, you often start with a spool of wire on hand and need to know how far it can reach before voltage drop exceeds 2%, 3%, or 5%. Solving the standard voltage drop equation for distance gives the exact one-way run limit.

DC & 1-phase: L_max = (V_sys × (%_limit / 100) × 1000 × N_parallel) / (2 × I × Z_eff) 3-phase AC: L_max = (V_sys × (%_limit / 100) × 1000 × N_parallel) / (√3 × I × Z_eff)

2%, 3%, and 5% targets: NEC Informational Notes 210.19(A) and 215.2(A) recommend keeping branch-circuit drop at 3% or less and total feeder-plus-branch drop at 5% or less. A tighter 2% budget is common for long feeders that still need 3% headroom for downstream branch circuits, or for sensitive electronics and DC inverters.

Ampacity always governs short runs: On short distances, a small wire (such as 14 AWG or 12 AWG) may easily stay within 3% voltage drop even when carrying far more current than its insulation can tolerate. Always confirm the Ampacity check column passes NEC Table 310.16 and 110.14(C) terminal limits before pulling wire.

Three worked maximum length examples

Example 1: 240 V single-phase 40 A load on 8 AWG copper

A 40 A 240 V single-phase load uses 8 AWG copper conductors (R_dc = 0.778 Ω/1000 ft at 75 °C from NEC Chapter 9 Table 8, 50 A at 75 °C).

3% drop budget = 240 V × 0.03 = 7.20 V L_max (3%) = (7.20 × 1000) / (2 × 40 A × 0.778 Ω/kft) = 115.7 ft (35.3 m) L_max (2%) = 77.1 ft | L_max (5%) = 192.8 ft

At 8 AWG copper, 40 A is within the 50 A 75 °C terminal rating, and the circuit can run up to 115.7 ft one-way while staying within the 3% branch-circuit guideline.

Example 2: 120 V 15 A detached garage branch circuit (12 AWG vs. 10 AWG copper)

A 120 V single-phase 15 A receptacle circuit feeds a detached garage (R_12 = 1.98 Ω/kft, R_10 = 1.24 Ω/kft). At 3% drop, allowable loss is 120 × 0.03 = 3.60 V.

12 AWG Cu: L_max (3%) = (3.60 × 1000) / (2 × 15 × 1.98) = 60.6 ft (18.5 m) 10 AWG Cu: L_max (3%) = (3.60 × 1000) / (2 × 15 × 1.24) = 96.8 ft (29.5 m)

If the trench is 85 ft one-way, 12 AWG exceeds 3% voltage drop; stepping up one gauge to 10 AWG copper extends the 3% reach to 96.8 ft.

Example 3: 480 V three-phase 100 A motor feeder in PVC conduit (1/0 AWG copper, PF 0.85)

A 480 V 3-phase feeder carries 100 A at 0.85 lagging power factor in PVC conduit on 1/0 AWG copper (Table 9: R = 0.12 Ω/kft, X_L = 0.044 Ω/kft, Z_eff = 0.1252 Ω/kft).

3% drop budget = 480 V × 0.03 = 14.40 V L_max (3%) = (14.40 × 1000) / (√3 × 100 × 0.1252) = 664.2 ft (202.4 m)

Three-phase 480 V power delivery extends the 3% maximum run length past 660 ft on 1/0 AWG copper while staying well inside its 150 A 75 °C rating.

Frequently asked questions

How is maximum wire run length calculated from voltage drop? Maximum one-way distance equals allowable voltage drop in volts times 1000 times parallel sets, divided by phase factor (2 for 1-phase/DC, 1.732 for 3-phase) times load amps times effective impedance per 1000 ft.
Does staying within the maximum wire length guarantee NEC compliance? No. Maximum run length only evaluates voltage drop. You must also ensure the conductor satisfies NEC Table 310.16 ampacity, 110.14(C) terminal temperature limits, and 240.4(D) overcurrent caps.
Why is the maximum run distance for 120 V half as long as 240 V at the same current? Because 3% of 120 V is 3.6 V while 3% of 240 V is 7.2 V. With twice the allowable volt drop for the same current and resistance per foot, the wire can run twice as far.