Temperature and bundling derating factors

NEC 310.15(B)(1) ambient temperature and 310.15(C)(1) conductor adjustment factors. Click any row to open it in the ampacity calculator.

NEC 310.15(B)(1) ambient temperature correction

23 rows
Ambient (°F) Alternate (°C°F) 60 °C
factor
75 °C
factor
90 °C
factor
Derated 90 °C
(10 AWG Cu)
Open in calculator

NEC 310.15(C)(1) conductor bundling adjustment

Current-carrying conductors Adjustment factor Percent of 310.16 Derated 90 °C (10 AWG Cu) Open in calculator

How ambient and bundling derating work together

Start from the insulation column: Both ambient temperature correction and bundling adjustment multiply the conductor’s unadjusted Table 310.16 ampacity in its insulation rating column (for example, the 90 °C column for THHN or XHHW-2). Then check the terminal temperature limit per 110.14(C); the usable ampacity is the lower of the two.
Combined formula: I_adj = I_table(insulation) × f_temp × f_bundle. Equipment grounding conductors and normally non-current-carrying neutrals are excluded from the conductor count under 310.15(E) and (F).