Breaker size calculator
Standard NEC 240.6(A) breaker or fuse rating, 125% continuous load factor, minimum conductor & EGC sizes, and GFCI/AFCI requirements.
Load and circuit details
Enter load, voltage, and duty cycle to size the circuit breaker.
- Required OCPD ampacity
- —
- Min copper wire
- —
- Min aluminum wire
- —
- Cu EGC (250.122)
- —
- Al EGC (250.122)
- —
- Load utilization
- —
GFCI / AFCI protection and standard breaker table
Select a room location to evaluate GFCI rules.
Select a room location to evaluate AFCI rules.
| Breaker (240.6) | Max cont. load (80%) | Min Cu wire | Min Al wire | Cu EGC (250.122) | Al EGC (250.122) |
|---|
—
IEC mode converts wire and EGC sizes to metric mm² using conservative NEC Table 310.16 and Table 250.122 equivalents; OCPD ratings follow NEC 240.6(A) standard steps.
NEC circuit breaker, wire, and protection sizing rules
Overcurrent protective devices (circuit breakers and fuses) protect conductors from overheating under overload and short-circuit faults. Under NEC 210.20(A) and 215.3, noncontinuous loads are sized at 100%, while continuous loads (operating for 3 hours or more) require multiplying by 125% before choosing the next standard rating in NEC 240.6(A).
I_load = Watts / (V × K_phase × PF) [K_phase = 1 for 1-ph/DC, √3 for 3-ph]
I_required = I_load × (1.25 if continuous else 1.00)
OCPD_rating = smallest NEC 240.6(A) standard rating ≥ I_required
Three worked breaker and fuse sizing examples
Example 1: 1,920 W commercial kitchen appliance at 120 V continuous
A 1,920 W warming cabinet runs continuously (≥ 3 hours) on a 120 V single-phase kitchen branch circuit with 75 °C terminals.
I_load = 1920 W / 120 V = 16.0 A
I_required = 16.0 A × 1.25 = 20.0 A
NEC 240.6(A) breaker = 20 A (1-pole)
Min wire: 12 AWG Cu (20 A 240.4(D) cap), EGC = 12 AWG Cu (Table 250.122)
In a dwelling kitchen, NEC 210.8(A)(6) requires GFCI and NEC 210.12(A) requires AFCI on this 120 V 20 A circuit, pointing to a 1-pole Dual-Function AFCI/GFCI breaker.
Example 2: 7,680 W (32 A) Level 2 EV charger in a garage at 240 V continuous
A 32 A (7,680 W) Level 2 EVSE is a continuous load by NEC 625.41, installed in a residential garage at 240 V single-phase.
I_load = 32.0 A
I_required = 32.0 A × 1.25 = 40.0 A
NEC 240.6(A) breaker = 40 A (2-pole)
Min wire (75 °C): 8 AWG Cu (50 A) or 6 AWG Al (50 A), EGC = 10 AWG Cu (8 AWG Al)
If connected via a 240 V receptacle in a garage, NEC 210.8(A)(2) and 625.54 require a 2-pole GFCI breaker. AFCI is not required on 240 V 40 A circuits.
Example 3: 45 kW 480 V 3-phase electric duct heater (non-continuous or continuous)
A 45,000 W 480 V 3-phase heater (PF = 1.00) treated as a continuous load with 75 °C lugs:
I_load = 45,000 / (480 × √3) = 54.13 A
I_required = 54.13 A × 1.25 = 67.66 A
Next standard NEC 240.6(A) OCPD = 70 A (3-pole)
Min wire (75 °C): 4 AWG Cu (85 A) or 3 AWG Al (75 A), EGC = 8 AWG Cu (6 AWG Al)
67.66 A rounds up to a 70 A 3-pole breaker under NEC 240.6(A), paired with a 8 AWG copper equipment grounding conductor from Table 250.122 (for 61–100 A OCPD).