Conduit size calculator

Fast single-circuit pipe sizer outputting the smallest legal NEC trade size and remaining spare fill capacity.

Circuit conductors

Conduit type (NEC Ch. 9 Table 4)
Conductor insulation (Table 5)
wires
wires
Raceway length
Minimum legal conduit size No result
— EMT

Select wire sizes and counts to size the conduit.

Actual fill %
—
NEC fill limit
—
Spare fill capacity
—
Total wire area
—
Conduit ID / total area
—
Next trade size up
—

Trade size comparison and spare capacity

Trade size Internal ID Max wire area Actual fill Spare area Status

IEC mode maps mm² conductors conservatively to NEC AWG gauges for Chapter 9 Table 5 outside dimensions and displays metric designators (mm) and mm² areas.

Advertisement

How to select minimum conduit size and spare capacity

Sizing conduit for a single feeder or branch circuit starts by adding the NEC Chapter 9 Table 5 cross-sectional areas of the ungrounded phase conductors, neutral (if present), and equipment grounding conductor. That total wire area is compared against the allowable fill area for each trade size in NEC Chapter 9 Table 4.

A_total = (N_phase × A_phase) + (N_ground × A_ground) Allowable_area = A_conduit_100% × Fill_limit (53% / 31% / 40% / 60%) Spare_area = Allowable_area − A_total Spare_fill_% = Fill_limit_% − (A_total / A_conduit_100% × 100)
Spare fill capacity for future circuits or pull ease: A trade size that lands at 38% or 39% fill is code legal, but leaves very little room for pulling bends or adding a spare conductor later. Checking both the minimum legal size and the next trade size up lets you balance material cost against pulling effort.

Three worked conduit sizing examples

Example 1: 50 A 240 V range/EV feeder in EMT (3 × 6 AWG + 1 × 10 AWG THHN)

A 240 V feeder with two hots and a neutral in 6 AWG THHN (0.0507 in² each) plus one 10 AWG THHN ground (0.0211 in²) is routed in EMT.

Total wire area = (3 × 0.0507) + 0.0211 = 0.1732 in² (4 wires → 40% limit) 1/2" EMT 40% limit = 0.122 in² (Too small, 57.0% fill) 3/4" EMT 40% limit = 0.213 in² (Minimum legal, 32.5% fill, 0.040 in² spare)

3/4" EMT is the smallest legal conduit at 32.5% fill, leaving 7.5% (0.040 in²) of spare capacity below the 40% cap.

Example 2: 200 A residential subpanel feeder in PVC Sch 80 (3 × 3/0 + 1 × 6 AWG XHHW)

Schedule 80 PVC has a thicker wall and smaller internal bore than Schedule 40 PVC. For three 3/0 XHHW (0.2642 in²) conductors and one 6 AWG XHHW ground (0.0590 in²):

Total wire area = (3 × 0.2642) + 0.0590 = 0.8516 in² 1-1/2" PVC Sch 80 40% limit = 0.684 in² (Too small, 49.8% fill) 2" PVC Sch 80 40% limit = 1.150 in² (Minimum legal, 29.6% fill, 0.298 in² spare)

2" PVC Schedule 80 is required (29.6% fill), providing generous spare margin and staying clear of the 2.8–3.2 jam zone (D/d = 3.30).

Example 3: 20 A branch circuit in RMC (2 × 12 AWG + 1 × 12 AWG THHN)

Two current-carrying 12 AWG THHN conductors and one 12 AWG THHN equipment ground (0.0133 in² each) inside rigid metal conduit (RMC).

Total wire area = 3 × 0.0133 = 0.0399 in² (3 wires → 40% limit) 1/2" RMC 40% limit = 0.314 × 0.40 = 0.1256 in² Actual fill = 0.0399 / 0.314 = 12.7% (27.3% / 0.0857 in² spare)

1/2" RMC handles this circuit at just 12.7% fill, leaving room for up to six more 12 AWG THHN conductors before hitting the 40% fill ceiling (subject to NEC 310.15(C) bundling derating).

Frequently asked questions

How is the minimum legal conduit trade size determined under the NEC? Add the Chapter 9 Table 5 areas of every conductor in the raceway, then choose the smallest Chapter 9 Table 4 trade size whose 53% (1 wire), 31% (2 wires), 40% (3+ wires), or 60% (nipple) fill area is at least that sum.
Should I include the equipment grounding conductor when sizing conduit? Yes. Every phase, neutral, and insulated or bare equipment grounding conductor counts toward both total area and total conductor count.
When should I step up one conduit size above the NEC minimum? Step up one size on long runs, pulls approaching 360 degrees of bends, when the jam ratio D/d sits between 2.8 and 3.2, or when future expansion is expected.