DC battery and inverter cable calculator

Size 12 V, 24 V, and 48 V battery-to-inverter and RV/marine/van DC cables from inverter wattage or DC amps, round-trip length, and 2%–3% drop limits, with Class T/ANL fuse sizing.

DC bank and load parameters

Common RV, van, marine & off-grid setups
Battery system voltage
Load entry mode
W
%
Inverter current calculation basis
DC draw at nominal voltage; cutoff mode sizes for depleted-battery current surge.
ft
One-way distance: 5.0 ft
%
Strict low-voltage drop preset
Battery chemistry
°F
Recommended copper DC battery cable No result
— Fine-stranded Cu (75 °C lug)

Enter system voltage, inverter watts or DC amps, and round-trip cable length.

Fuse / breaker (Class T vs ANL) —
Sizes overcurrent protection within 7 in (18 cm) of the battery positive post.
Governing limit & ampacity —
Compares NEC 310.16 75 °C terminal rating against strict 2%–3% voltage drop.
DC load current
—
125% design current
—
Recommended fuse
—
Round-trip voltage drop
—
Voltage at inverter
—
Cable power loss
—

4 AWG through 4/0 AWG cable comparison

Cable size (Cu) 75 °C NEC 90 °C adj. Drop % Volts lost Power lost Assessment

IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance at 75 °C for DC voltage drop.

Advertisement

Sizing 12 V, 24 V, and 48 V DC battery and inverter cables

Low-voltage DC circuits carry dramatically higher current per kilowatt than 120 V or 240 V AC circuits, and even a half-volt drop in a 12 V bank can trigger an inverter low-voltage alarm under heavy surge loads.

Inverter DC current: I_dc = P_ac / (V_dc × η_inv) Continuous design current: I_design = I_dc × 1.25 Round-trip voltage drop: V_drop = I_dc × R_75C_per_kft × (L_roundtrip / 1000) / N_parallel Percent drop: %VD = (V_drop / V_dc) × 100 ≤ 2% (inverter) or 3% (general DC)

Why 4 AWG through 4/0 AWG dominates battery wiring: Small DC loads use 10 AWG to 6 AWG, while battery-to-inverter and DC busbar trunks almost always land between 4 AWG and 4/0 AWG fine-stranded copper (such as UL 1426 marine tinned copper or NEC RHH/RHW-2 / welding cable rated for battery lugs). When continuous 125% current exceeds a single 4/0 AWG conductor's 230 A (75 °C terminal) rating—typical on 3000 W+ 12 V inverters—install two matched parallel cables per pole (such as 2 × 2/0 AWG or 2 × 4/0 AWG) of identical length and crimp lug termination per NEC 310.10(G).

Class T vs. ANL fuse selection: Always place the main battery fuse as close as practical to the positive battery post (within 7 inches in marine ABYC E-11, or 18 inches in RV/automotive). LiFePO4 battery packs can deliver 5,000–20,000 A into a short circuit; always use a Class T fuse (20,000 A AIC) on LiFePO4 and 48 V systems, while ANL or Mega fuses are suitable for 12 V / 24 V AGM and flooded lead-acid auxiliary circuits.

12 V / 24 V / 48 V Inverter cable & fuse quick reference (10 ft round-trip, 85% eff.)

System Inverter W DC draw 125% design Fuse (240.6) Copper cable (75 °C) Drop (10 ft RT)

Three worked DC battery and inverter cable examples

Example 1: 12 V 2000 W camper van inverter, 10 ft round-trip (LiFePO4)

A 2000 W pure-sine inverter (85% efficiency) sits 5 ft one-way (10 ft round-trip positive + negative) from a 12 V LiFePO4 battery bank under a 2% maximum voltage drop target.

DC current = 2000 W / (12 V × 0.85) = 196.1 A 125% design current = 196.1 A × 1.25 = 245.1 A → 250 A Class T fuse 75 °C Cu NEC 310.16: 2 × 1/0 AWG parallel = 300 A (0.96% drop, 0.12 V lost); single 4/0 AWG = 230 A @ 75 °C (260 A @ 90 °C) 4/0 AWG Cu drop (10 ft RT): 196.1 A × 0.0608 × 0.010 = 0.119 V (0.99% ≤ 2%, pass)

Under strict NEC 75 °C terminal limits (245.1 A required > 230 A of single 4/0), the calculator selects 2 × 1/0 AWG copper parallel sets (300 A capacity, 0.96% drop / 0.12 V lost), while in 90 °C / 105 °C free-air marine/RV battery service a single 4/0 AWG copper cable (260 A+, 0.99% drop) is also commonly used with a 250 A Class T fuse at the LiFePO4 positive terminal.

Example 2: 24 V 3000 W off-grid cabin inverter, 12 ft round-trip

Stepping up to 24 V doubles voltage and halves DC current for a 3000 W inverter (85% efficiency) located 6 ft from the battery bank (12 ft round-trip).

DC current = 3000 W / (24 V × 0.85) = 147.1 A 125% design current = 147.1 A × 1.25 = 183.8 A → 200 A Class T fuse 75 °C Cu NEC 310.16: 3/0 AWG Cu = 200 A (passes 183.8 A & 200 A fuse) 3/0 AWG Cu drop (12 ft RT): 147.1 A × 0.0766 × 0.012 = 0.135 V (0.56% ≤ 2%)

Use 3/0 AWG copper with a 200 A Class T fuse—easily fitting single-cable lugs with only 0.56% voltage drop (0.14 V).

Example 3: 12 V 80 A DC fridge/heater/lights trunk, 30 ft round-trip (3% drop)

A marine/RV auxiliary DC distribution panel draws up to 80 A at 12 V and is mounted 15 ft forward of the AGM battery bank (30 ft round-trip) with a strict 3% (0.36 V) drop limit.

125% design current = 80 A × 1.25 = 100.0 A → 100 A ANL or Class T fuse Ampacity minimum (75 °C): 3 AWG Cu = 100 A (or 2 AWG Cu = 115 A) Drop on 3 AWG (30 ft RT): 80 A × 0.245 × 0.030 = 0.588 V (4.90% > 3%, FAIL!) Drop on 1 AWG (30 ft RT): 80 A × 0.154 × 0.030 = 0.370 V (3.08% > 3%, FAIL!) Drop on 1/0 AWG (30 ft RT): 80 A × 0.122 × 0.030 = 0.293 V (2.44% ≤ 3%, PASS!)

Even though 3 AWG carries 100 A thermally, the 30 ft round-trip at 12 V forces upsizing three sizes to 1/0 AWG copper (or 2/0 AWG for < 2% drop) protected by a 100 A ANL or Class T fuse.

Frequently asked questions

Why is round-trip length used for 12V, 24V, and 48V DC battery cable sizing? Current travels out on the positive cable and returns on the negative cable. Voltage drop occurs across both conductors in series, so you must use the full round-trip length (positive + negative) when computing DC drop.
When should I use a Class T fuse instead of an ANL fuse on a battery bank? LiFePO4 lithium batteries and 48 V systems require a high-AIC Class T fuse (20,000 A interrupting rating, 125–160 V DC) because lithium short-circuit current can exceed an ANL fuse's breaking capacity. ANL/Mega fuses are limited to 12 V / 24 V AGM or lead-acid banks.
What size cable do I need for a 3000W inverter at 12V vs 24V vs 48V? At 85% efficiency, 3000 W draws ~294 A at 12 V (requiring parallel 2/0 or 4/0 AWG under NEC 310.16), ~147 A at 24 V (3/0 AWG copper), and ~74 A at 48 V (3 AWG or 2 AWG copper).

Related calculators and reference charts

DC Cable / Fuse —
No result View