Solar PV string and array wire size calculator
Size PV source and output conductors using NEC 690.8 1.56x Isc current scaling, rooftop conduit derating, cold-weather Voc string limits, and 1%–2% voltage drop.
PV array and site parameters
Enter module STC ratings, string count, and rooftop conditions.
- 1.56x Isc design (690.8)
- —
- Cold Voc / Vmp array
- —
- Derated 90 °C ampacity
- —
- Voltage drop (at Vmp)
- —
- DC power loss / OCPD
- —
- Min EMT / EGC (250.122)
- —
String summary and conductor comparison
| Size | 75 °C term. | 90 °C derated | Drop % | Volts lost | Power lost | Status |
|---|
IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance adjusted to conductor operating temperature for voltage drop.
NEC Article 690 solar PV conductor and string sizing method
Solar photovoltaic circuits experience sustained high irradiance, elevated rooftop conduit temperatures, and cold-morning open-circuit voltage spikes. NEC Article 690 requires checking thermal ampacity, rooftop derating, cold Voc limits, and DC voltage drop together.
Maximum circuit current (690.8(A)): I_max = Isc × N_parallel × 1.25
Continuous conductor/OCPD factor (690.8(B)): I_156 = I_max × 1.25 = Isc × N_parallel × 1.56
Terminal & unadjusted check: I_75C ≥ I_156 (110.14(C))
Rooftop derated check (90 °C): I_90C × f_temp × f_bundle ≥ I_max (690.8(B)(1))
Cold-weather Voc (690.7(A)): Voc_cold = N_series × Voc_stc × [1 + (β/100) × (T_min_C - 25)]
DC voltage drop: %VD = (2 × I_mp_total × R × L / 1000) / Vmp_string × 100
Why two ampacity checks? Under NEC 690.8(B)(1), you do not stack the 1.25 continuous factor on top of rooftop ambient/bundling derating unless an overcurrent device requires protection at its rating. Conductors must satisfy both the unadjusted 1.56x Isc requirement (capped at 75 °C equipment terminals per 110.14(C)) and the 1.25x Isc requirement after applying 90 °C Table 310.15(B)(1) ambient correction and 310.15(C)(1) bundling factors. Where 3 or more parallel strings are combined in a combiner box, string fuses rated at least 1.56x Isc (per module max series fuse rating) are required.
Target 1%–2% DC voltage drop: While NEC 210.19 informational notes suggest 3% for general branch circuits, solar PV designers target 1% to 2% DC drop from array to inverter because every watt lost in string wiring reduces daily energy harvest and can push MPPT trackers below optimal voltage on hot roofs.
Quick reference: 1.56x Isc and 90 °C rooftop derating (Copper)
| Circuit Isc | 1.25x Imax | 1.56x (690.8) | Std OCPD | Min Cu (30 °C) | Cu @ 60 °C, 4 CCC | Cu EGC (250.122) |
|---|
Three worked solar PV sizing examples
Example 1: Residential 10-panel 600 V rooftop string in conduit, 80 ft
Ten 400 W modules (Isc = 11.5 A, Imp = 10.8 A, Voc = 49.5 V, Vmp = 41.5 V, β = -0.28%/°C) run 80 ft through 3/4" EMT raised ≥ 7/8" above a roof at 104 °F (40 °C) ambient with 2 strings (4 CCC) in the conduit and a -10 °C (14 °F) winter low.
Cold Voc = 10 × 49.5 × [1 + (-0.0028) × (-10 - 25)] = 495 × 1.098 = 543.5 V (≤ 600 V, pass)
NEC 690.8 1.56x Isc = 11.5 × 1.56 = 17.94 A; I_max = 11.5 × 1.25 = 14.38 A
10 AWG Cu (90 °C = 40 A): 40 × 0.91 (40 °C) × 0.80 (4 CCC) = 29.12 A ≥ 14.38 A; 75 °C = 35 A ≥ 17.94 A
DC drop (10 AWG Cu @ 415 Vmp, 10.8 A, 80 ft): 2 × 10.8 × 1.24 × 0.080 / 415 = 0.52% (≤ 2%, pass)
10 AWG copper THWN-2 / PV Wire passes both the 690.8 ampacity/derating rules and stays well under the 2% voltage drop limit (only 0.52% loss, 21.4 W).
Example 2: Cold-weather Voc overvoltage check at -25 °C (-13 °F)
Suppose a designer puts 12 of the same 49.5 V Voc modules in series on a residential 600 V inverter in a northern climate where record winter lows hit -25 °C (-13 °F).
STC string Voc = 12 × 49.5 V = 594.0 V (looks under 600 V on paper!)
Cold correction factor = 1 + (-0.0028) × (-25 - 25) = 1 + 0.140 = 1.140 (+14.0%)
Cold Voc = 594.0 V × 1.140 = 677.2 V (> 600 V NEC 690.7(A) FAIL!)
Max modules under 600 V = floor(600 / (49.5 × 1.140)) = floor(10.63) = 10 modules
Even though 12 panels have an STC Voc of 594 V, cold winter temperatures drive open-circuit voltage to 677.2 V—violating NEC 690.7 and risking inverter failure. Reduce the string to 10 modules (564.3 V at -25 °C) or split into two 6-module strings.
Example 3: 3-string combined PV output circuit, 220 ft ground mount (1.5% drop)
Three parallel strings of 500 W panels (Isc = 13.8 A, Imp = 13.0 A, Vmp_string = 360 V) combine in a DC combiner box and feed an inverter 220 ft away with a strict 1.5% DC voltage drop target.
Combined current: Isc_total = 3 × 13.8 = 41.4 A; Imp_total = 3 × 13.0 = 39.0 A
NEC 690.8 1.56x Isc = 41.4 × 1.56 = 64.6 A → 70 A DC breaker / disconnect
75 °C Cu ampacity min: 4 AWG Cu = 85 A (6 AWG Cu = 65 A passes 64.6 A, but drop at 220 ft is 2.34% > 1.5%)
4 AWG Cu drop = 2 × 39.0 × 0.308 × 0.220 / 360 = 1.47% (≤ 1.5%, pass)
While 6 AWG copper satisfies the 64.6 A ampacity requirement, voltage drop over 220 ft pushes the design up to 4 AWG copper (1.47% drop, 206 W loss) with an 8 AWG copper EGC per NEC 250.122 (or 6 AWG if upsized per 250.122(B)).