Maximum wire run length calculator
Longest one-way conductor run in feetmeters before exceeding 2%, 3%, or 5% voltage drop, plus all standard gauges side by side.
Circuit parameters
Enter voltage, load current, and wire size to compute maximum distance.
- Max run at 2% drop
- —
- Max run at 3% drop
- —
- Max run at 5% drop
- —
- Allowable volts lost
- —
- 75 °C wire ampacity
- —
- Effective R / Z_eff
- —
Max distance across all standard gauges
Click any row to select that gauge above. Highlighted row is the active selection.
| Gauge | 75 °C (A) | DC R (Ω/kft) | Max @ 2% | Max @ 3% | Max @ 5% | Ampacity check |
|---|
—
In IEC mode, Table 8 DC calculations use IEC 60228 resistance adjusted from 20 °C to 75 °C; NEC 75 °C ampacity uses the conservative AWG size that does not exceed the metric cross-section.
Maximum run length formula and NEC considerations
When laying out a feeder, outbuilding subpanel, EV charger, or remote pump, you often start with a spool of wire on hand and need to know how far it can reach before voltage drop exceeds 2%, 3%, or 5%. Solving the standard voltage drop equation for distance gives the exact one-way run limit.
DC & 1-phase: L_max = (V_sys × (%_limit / 100) × 1000 × N_parallel) / (2 × I × Z_eff)
3-phase AC: L_max = (V_sys × (%_limit / 100) × 1000 × N_parallel) / (√3 × I × Z_eff)
2%, 3%, and 5% targets: NEC Informational Notes 210.19(A) and 215.2(A) recommend keeping branch-circuit drop at 3% or less and total feeder-plus-branch drop at 5% or less. A tighter 2% budget is common for long feeders that still need 3% headroom for downstream branch circuits, or for sensitive electronics and DC inverters.
Three worked maximum length examples
Example 1: 240 V single-phase 40 A load on 8 AWG copper
A 40 A 240 V single-phase load uses 8 AWG copper conductors (R_dc = 0.778 Ω/1000 ft at 75 °C from NEC Chapter 9 Table 8, 50 A at 75 °C).
3% drop budget = 240 V × 0.03 = 7.20 V
L_max (3%) = (7.20 × 1000) / (2 × 40 A × 0.778 Ω/kft) = 115.7 ft (35.3 m)
L_max (2%) = 77.1 ft | L_max (5%) = 192.8 ft
At 8 AWG copper, 40 A is within the 50 A 75 °C terminal rating, and the circuit can run up to 115.7 ft one-way while staying within the 3% branch-circuit guideline.
Example 2: 120 V 15 A detached garage branch circuit (12 AWG vs. 10 AWG copper)
A 120 V single-phase 15 A receptacle circuit feeds a detached garage (R_12 = 1.98 Ω/kft, R_10 = 1.24 Ω/kft). At 3% drop, allowable loss is 120 × 0.03 = 3.60 V.
12 AWG Cu: L_max (3%) = (3.60 × 1000) / (2 × 15 × 1.98) = 60.6 ft (18.5 m)
10 AWG Cu: L_max (3%) = (3.60 × 1000) / (2 × 15 × 1.24) = 96.8 ft (29.5 m)
If the trench is 85 ft one-way, 12 AWG exceeds 3% voltage drop; stepping up one gauge to 10 AWG copper extends the 3% reach to 96.8 ft.
Example 3: 480 V three-phase 100 A motor feeder in PVC conduit (1/0 AWG copper, PF 0.85)
A 480 V 3-phase feeder carries 100 A at 0.85 lagging power factor in PVC conduit on 1/0 AWG copper (Table 9: R = 0.12 Ω/kft, X_L = 0.044 Ω/kft, Z_eff = 0.1252 Ω/kft).
3% drop budget = 480 V × 0.03 = 14.40 V
L_max (3%) = (14.40 × 1000) / (√3 × 100 × 0.1252) = 664.2 ft (202.4 m)
Three-phase 480 V power delivery extends the 3% maximum run length past 660 ft on 1/0 AWG copper while staying well inside its 150 A 75 °C rating.