Voltage drop calculator
Volts lost, percent drop, load-end voltage, and minimum compliant wire size using NEC Chapter 9 Tables 8 and 9.
Circuit parameters
Enter voltage, load, and distance to calculate drop.
- Volts lost
- —
- End voltage at load
- —
- Min wire for 3% drop
- —
- Min wire for 5% drop
- —
- 75 °C wire ampacity
- —
- Cable loss / Z_eff
- —
Adjacent wire gauge comparison and working
| Gauge | Effective Z / R | Volts lost | Drop % | End voltage | 3% / 5% status |
|---|
—
In IEC mode, Table 8 DC calculations use IEC 60228 resistance adjusted from 20 °C to 75 °C; Table 9 AC reactance uses the nearest AWG equivalent conduit reactance.
Voltage drop formulas and NEC recommendations
Voltage drop occurs because every practical conductor has electrical resistance (and in AC circuits, inductive reactance). As current flows to the load and returns to the source, a fraction of the supply voltage is dissipated as heat in the wire, reducing the terminal voltage available to motors, lighting, heaters, and power supplies.
DC & 1-phase: V_drop = (2 × I × Z_eff × L) / (1000 × N_parallel)
3-phase AC: V_drop = (√3 × I × Z_eff × L) / (1000 × N_parallel)
Effective AC impedance: Z_eff = R_ac × PF + X_L × sin(arccos(PF))
NEC 3% and 5% limits: NEC Informational Notes 210.19(A) and 215.2(A) recommend keeping branch-circuit voltage drop at 3% or less and total combined feeder-plus-branch drop at 5% or less. Excessive drop causes induction motors to draw higher current and run hot, dims incandescent and halogen lighting, and can cause electronic power supplies or EV chargers to fault on undervoltage.
Three worked voltage drop examples
Example 1: 240 V single-phase 40 A load at 75 ft (8 AWG copper)
A 40 A resistive workshop load runs 75 ft one-way from a 240 V single-phase panel on 8 AWG copper conductors (R_dc = 0.778 Ω/1000 ft at 75 °C from NEC Chapter 9 Table 8).
V_drop = 2 × 40 A × 0.778 Ω/kft × (75 / 1000) = 4.67 V
% Drop = (4.67 / 240) × 100 = 1.95% (Within 3% limit)
End voltage = 240 − 4.67 = 235.3 V
At 1.95%, this circuit comfortably satisfies both the 3% branch-circuit and 5% total voltage drop guidelines, while 8 AWG copper (50 A at 75 °C) satisfies ampacity.
Example 2: 480 V three-phase 100 A feeder in PVC conduit at PF 0.85
A 480 V 3-phase motor control feeder supplies 100 A at 0.85 lagging power factor over 250 ft of 1/0 AWG copper in PVC conduit (Table 9: R = 0.12 Ω/kft, X_L = 0.044 Ω/kft).
sin(arccos(0.85)) = 0.5268
Z_eff = (0.12 × 0.85) + (0.044 × 0.5268) = 0.1252 Ω/kft
V_drop = √3 × 100 A × 0.1252 × (250 / 1000) = 5.42 V
% Drop = (5.42 / 480) × 100 = 1.13% (End voltage = 474.6 V)
High system voltage and 3-phase geometry keep the drop to 1.13%, leaving nearly 4% of drop budget for downstream branch circuits.
Example 3: 24 V DC battery-to-inverter run at 30 A over 40 ft
A 24 V DC off-grid circuit draws 30 A across 40 ft one-way (80 ft round trip) using 10 AWG copper (R = 1.24 Ω/kft).
V_drop = 2 × 30 A × 1.24 × (40 / 1000) = 2.98 V
% Drop = (2.98 / 24) × 100 = 12.40% (End voltage = 21.0 V, FAIL)
Minimum compliant wire for 3% (≤ 0.72 V): 3 AWG Cu (2.45% drop)
Low-voltage DC circuits suffer severe percent drop even over modest distances. Although 10 AWG copper safely carries 30 A thermally, holding voltage drop under 3% at 24 V requires upsizing to 3 AWG copper.