Wirebench
AWG, ft, °Fmm², m, °C

Voltage drop calculator

Volts lost, percent drop, load-end voltage, and minimum compliant wire size using NEC Chapter 9 Tables 8 and 9.

Circuit parameters

Phase
V
ft
A
PF
Unity (1.00) resistive
Conductor material
Impedance model / conduit
Chapter 9 Table 8 DC resistance at 75 °C.
Voltage drop No result
— %

Enter voltage, load, and distance to calculate drop.

3% branch (210.19): —
5% total (215.2): —
Volts lost
—
End voltage at load
—
Min wire for 3% drop
—
Min wire for 5% drop
—
75 °C wire ampacity
—
Cable loss / Z_eff
—

Adjacent wire gauge comparison and working

Gauge Effective Z / R Volts lost Drop % End voltage 3% / 5% status
—

In IEC mode, Table 8 DC calculations use IEC 60228 resistance adjusted from 20 °C to 75 °C; Table 9 AC reactance uses the nearest AWG equivalent conduit reactance.

Advertisement

Voltage drop formulas and NEC recommendations

Voltage drop occurs because every practical conductor has electrical resistance (and in AC circuits, inductive reactance). As current flows to the load and returns to the source, a fraction of the supply voltage is dissipated as heat in the wire, reducing the terminal voltage available to motors, lighting, heaters, and power supplies.

DC & 1-phase: V_drop = (2 × I × Z_eff × L) / (1000 × N_parallel) 3-phase AC: V_drop = (√3 × I × Z_eff × L) / (1000 × N_parallel) Effective AC impedance: Z_eff = R_ac × PF + X_L × sin(arccos(PF))

NEC 3% and 5% limits: NEC Informational Notes 210.19(A) and 215.2(A) recommend keeping branch-circuit voltage drop at 3% or less and total combined feeder-plus-branch drop at 5% or less. Excessive drop causes induction motors to draw higher current and run hot, dims incandescent and halogen lighting, and can cause electronic power supplies or EV chargers to fault on undervoltage.

Conduit material and AC reactance (NEC Chapter 9 Table 9): Magnetic steel conduit increases inductive reactance (X_L) and eddy-current losses compared to non-magnetic PVC or aluminum conduit. On small branch circuits (14 to 8 AWG), DC resistance dominates; on large feeders (1/0 AWG and up) at lagging power factors, using Table 9 AC impedance is essential for an accurate prediction.

Three worked voltage drop examples

Example 1: 240 V single-phase 40 A load at 75 ft (8 AWG copper)

A 40 A resistive workshop load runs 75 ft one-way from a 240 V single-phase panel on 8 AWG copper conductors (R_dc = 0.778 Ω/1000 ft at 75 °C from NEC Chapter 9 Table 8).

V_drop = 2 × 40 A × 0.778 Ω/kft × (75 / 1000) = 4.67 V % Drop = (4.67 / 240) × 100 = 1.95% (Within 3% limit) End voltage = 240 − 4.67 = 235.3 V

At 1.95%, this circuit comfortably satisfies both the 3% branch-circuit and 5% total voltage drop guidelines, while 8 AWG copper (50 A at 75 °C) satisfies ampacity.

Example 2: 480 V three-phase 100 A feeder in PVC conduit at PF 0.85

A 480 V 3-phase motor control feeder supplies 100 A at 0.85 lagging power factor over 250 ft of 1/0 AWG copper in PVC conduit (Table 9: R = 0.12 Ω/kft, X_L = 0.044 Ω/kft).

sin(arccos(0.85)) = 0.5268 Z_eff = (0.12 × 0.85) + (0.044 × 0.5268) = 0.1252 Ω/kft V_drop = √3 × 100 A × 0.1252 × (250 / 1000) = 5.42 V % Drop = (5.42 / 480) × 100 = 1.13% (End voltage = 474.6 V)

High system voltage and 3-phase geometry keep the drop to 1.13%, leaving nearly 4% of drop budget for downstream branch circuits.

Example 3: 24 V DC battery-to-inverter run at 30 A over 40 ft

A 24 V DC off-grid circuit draws 30 A across 40 ft one-way (80 ft round trip) using 10 AWG copper (R = 1.24 Ω/kft).

V_drop = 2 × 30 A × 1.24 × (40 / 1000) = 2.98 V % Drop = (2.98 / 24) × 100 = 12.40% (End voltage = 21.0 V, FAIL) Minimum compliant wire for 3% (≤ 0.72 V): 3 AWG Cu (2.45% drop)

Low-voltage DC circuits suffer severe percent drop even over modest distances. Although 10 AWG copper safely carries 30 A thermally, holding voltage drop under 3% at 24 V requires upsizing to 3 AWG copper.

Frequently asked questions

Are the NEC 3% and 5% voltage drop limits mandatory? Informational Notes to NEC 210.19(A) and 215.2(A) recommend 3% for branch circuits and 5% total for feeders plus branch circuits. While advisory in the NEC body, local building codes, energy codes, and equipment listings often enforce them.
When does NEC Chapter 9 Table 9 AC impedance matter compared to Table 8 DC resistance? For 14 through 6 AWG at unity power factor, both tables yield almost identical drops. For 1/0 AWG and larger AC feeders, skin effect and conduit reactance in Table 9 noticeably increase effective impedance, especially at lower power factors.
Why is the phase factor 2 for single-phase and DC but square root of 3 for three-phase? Single-phase and DC circuits carry full current out and back over two conductors (factor 2), whereas a balanced three-phase system relates line-to-line drop to conductor impedance by the square root of 3 (1.732).