Submersible well pump wire size calculator
Size 1/2 HP to 5 HP submersible pump cables (2-wire or 3-wire with control box) across combined trench run and well depth under strict voltage drop limits.
Well pump & run parameters
Select motor horsepower, trench run, and vertical well depth.
- Voltage drop
- —
- Voltage at motor
- —
- Max length at this size
- —
- 125% NEC 430.22
- —
- Breaker (NEC 430.52)
- —
- EGC (250.122 / 250.122(B))
- —
Materials take-off list
| Segment / item | Cable / hardware specification | Qty / Length |
|---|
IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance adjusted to 75 °C for voltage drop.
How submersible well pump wire is sized under NEC Article 430
Submersible well pumps almost always hit voltage drop limits long before thermal ampacity limits because the circuit combines an outdoor buried trench run with a vertical drop down the borehole.
L_total = L_trench + L_well_depth
I_ampacity = 1.25 × max(I_FLC_430.248, I_SFA_nameplate) (NEC 430.22)
%VD = (2 × I_SFA × R_75C × L_total / 1000) / V_system × 100 ≤ 3%
2-wire vs. 3-wire with control box: A 2-wire submersible motor contains an internal start switch and runs on two power conductors plus an insulated green EGC (1/2 HP to 1-1/2 HP). A 3-wire submersible motor places the start capacitor and potential relay in an above-ground control box; the trench run from the pressure switch to the control box still uses 2 power conductors plus EGC, while the down-well submersible cable uses 3 power conductors (Black, Red, Yellow) plus green EGC.
NEC 250.122(B) ground upsizing warning: Whenever you step up the power conductors for voltage drop (for example, from 12 AWG code minimum to 8 AWG), NEC 250.122(B) requires increasing the equipment grounding conductor proportionally by circular mil area. Factory flat submersible cables often mold a smaller ground wire (such as 10 AWG ground inside 8/3 w/G); if 250.122(B) requires a full-size EGC, install individual THW/XHHW submersible conductors with a compliant green copper ground.
Maximum combined run length (ft) at 3% drop, 75 °C Copper
| Pump rating | NEC FLC / SFA | Breaker (430.52) | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|
Three worked submersible well pump examples
Example 1: 1 HP 230 V 3-wire pump, 120 ft trench + 200 ft well depth
A 1 HP 230 V 3-wire submersible pump (8.0 A NEC 430.248 FLC, 9.8 A max SFA) sits 200 ft down a borehole fed by a 120 ft trench from the house pressure tank, under a 3% drop limit.
Combined one-way length = 120 ft + 200 ft = 320 ft
NEC 430.22 ampacity = 9.8 A × 1.25 = 12.3 A (14/12 AWG Cu thermal min; 20 A breaker)
12 AWG Cu drop = 2 × 9.8 × 1.98 × 0.320 / 230 = 5.40% (> 3%, fail)
10 AWG Cu drop = 2 × 9.8 × 1.24 × 0.320 / 230 = 3.38% (> 3%, fail)
8 AWG Cu drop = 2 × 9.8 × 0.778 × 0.320 / 230 = 2.12% (≤ 3%, pass)
Use 8 AWG copper: 8/2 w/G UF-B (or 8 AWG THWN-2 in PVC) for the 120 ft trench to the control box, and 8/3 w/G submersible cable for the 200 ft well drop, with EGC upsized per NEC 250.122(B).
Example 2: 1/2 HP 115 V 2-wire pump, 60 ft trench + 100 ft well depth
A shallow-well 1/2 HP 115 V 2-wire pump (12.0 A SFA, 9.8 A NEC FLC) is 60 ft from the cabin panel at 100 ft depth (160 ft total) with a 3% voltage drop target.
Combined length = 60 ft + 100 ft = 160 ft
NEC 430.22 ampacity = 12.0 A × 1.25 = 15.0 A (20 A 1-pole breaker)
10 AWG Cu drop = 2 × 12.0 × 1.24 × 0.160 / 115 = 4.14% (> 3%, fail)
8 AWG Cu drop = 2 × 12.0 × 0.778 × 0.160 / 115 = 2.60% (≤ 3%, pass)
Notice how 115 V requires twice the current and has half the voltage headroom of 230 V—forcing 8 AWG copper at just 160 ft, whereas the exact same 1/2 HP motor in 230 V (6.0 A SFA) runs 160 ft comfortably on 12 AWG copper (1.65% drop).
Example 3: 3 HP 230 V 3-wire deep well, 150 ft trench + 450 ft well depth
A 3 HP 230 V 3-wire submersible pump (17.0 A FLC/SFA) is set 450 ft deep with a 150 ft trench (600 ft total one-way run) and a 3% maximum voltage drop.
Combined length = 150 ft + 450 ft = 600 ft
NEC 430.22 ampacity = 17.0 A × 1.25 = 21.3 A (30 A 2-pole breaker)
6 AWG Cu drop = 2 × 17.0 × 0.491 × 0.600 / 230 = 4.35% (> 3%)
4 AWG Cu drop = 2 × 17.0 × 0.308 × 0.600 / 230 = 2.73% (≤ 3%, pass)
600 ft combined run at 17.0 A requires 4 AWG copper conductors and a 30 A 2-pole breaker paired with a 3 HP 230 V control box. Under NEC 250.122(A) & (B), upsize the 10 AWG base EGC proportionally to 4 AWG copper (matching the 4 AWG circuit conductors).