Watts, volts, amps, kVA and HP converter

Bidirectional conversion across Watts, kW, kVA, Volts, Amps, and Horsepower for DC, 1-phase AC, and 3-phase AC with PF and efficiency.

Electrical quantities

System type
Bidirectional mode
Edit any load field (A, W, kW, kVA, or HP) to update all others.
V
A
W
kW
kVA
HP
PF
Lagging AC PF
%
Used for shaft HP
Electrical power conversion No result
— kW

Enter voltage and any power or current quantity to convert across all units.

Line current
—
Real power (P)
—
Apparent power (S)
—
Reactive power (Q)
—
Shaft output (HP)
—
Next std OCPD (240.6)
—

Same power across standard NEC voltages

Click any voltage row to apply it. Wire sizes assume 75 °C copper terminals, 30 °C ambient, and 100% non-continuous duty.

System voltage Current (A) 125% cont. (A) Next OCPD Min Cu wire (75 °C) Load impedance
—

IEC mode shows conservative AWG equivalents mapped to metric mm² from NEC Table 310.16; power formulas are identical in SI and US units.

Advertisement

Electrical power equations for DC, 1-phase, and 3-phase

Electrical power conversion links line voltage (V), line current (I), power factor (PF), and phase configuration (K = 1 for DC or 1-phase AC, K = √3 ≈ 1.732 for balanced 3-phase AC). Motor efficiency (η) relates electrical input watts to mechanical shaft horsepower (1 HP = 745.7 W).

DC (PF = 1): P_W = V × I | I = P_W / V | V = P_W / I | kVA = kW 1-Phase AC: S_kVA = (V × I) / 1000 | P_kW = S_kVA × PF | Q_kVAR = √(S_kVA² - P_kW²) I = (P_kW × 1000) / (V × PF) | V = (P_kW × 1000) / (I × PF) 3-Phase AC: S_kVA = (√3 × V_LL × I) / 1000 | P_kW = S_kVA × PF I = (P_kW × 1000) / (√3 × V_LL × PF) | V_LL = (P_kW × 1000) / (√3 × I × PF) Mechanical Horsepower (1 HP = 745.7 W): HP = (P_W × η) / 745.7 | P_W = (HP × 745.7) / η
Note on NEC motor branch circuits (Article 430): This converter calculates actual electrical operating current from mechanical HP, efficiency, and power factor. When sizing conductors and branch breakers for AC motors under NEC Article 430, code rules require using NEC Table 430.248 (1-phase) or Table 430.250 (3-phase) full-load currents (FLC) rather than calculated nameplate amps.

Three worked power conversion examples

Example 1: 10 HP 3-phase 480 V motor at 0.85 PF and 90% efficiency

Convert a 10 HP mechanical load on a 480 V 3-phase feeder with 90% motor efficiency and 0.85 lagging power factor into electrical kW, kVA, and line current.

Shaft output = 10 HP × 745.7 W/HP = 7,457 W (7.46 kW_mech) Input real power = 7,457 W / 0.90 = 8,285.6 W (8.29 kW_elec) Apparent power = 8.286 kW / 0.85 PF = 9.75 kVA | Reactive = 5.13 kVAR Line current = 8,285.6 / (480 × √3 × 0.85) = 11.72 A

The motor draws 11.72 A line current and 9.75 kVA of transformer capacity while delivering 10 HP at the shaft.

Example 2: 9.6 kW load at 240 V 1-phase vs. 208 V 1-phase (PF = 1.00)

Compare line current for a 9,600 W resistive EVSE or water heater supplied at 240 V residential vs. 208 V commercial single-phase.

At 240 V 1-ph: I = 9,600 W / (240 V × 1.00) = 40.0 A (50 A cont. OCPD) At 208 V 1-ph: I = 9,600 W / (208 V × 1.00) = 46.15 A (60 A cont. OCPD)

Dropping from 240 V to 208 V increases current by 15.4% for the same kW, pushing a continuous 9.6 kW load from a 50 A circuit into a 60 A circuit.

Example 3: Bidirectional voltage solve — 15 kVA 3-phase load at 36.1 A

A balanced 3-phase machine draws 36.1 A at 15.0 kVA apparent power (0.80 PF = 12.0 kW). Switch mode to Solve Volts to identify the supply voltage.

V_LL = (15.0 kVA × 1000) / (√3 × 36.1 A) = 239.9 V → 240 V 3-phase Real power = 15.0 × 0.80 = 12.0 kW | Reactive power = 9.0 kVAR

Solving voltage from kVA and Amps confirms a 240 V three-phase supply without needing to know PF in advance (since S = √3 × V × I).

Frequently asked questions

What is the difference between kW and kVA? Kilowatts (kW) represent real working power, while kVA represents total apparent power (voltage × current). They are linked by Power Factor: kW = kVA × PF. Transformers and generators are rated in kVA because heating depends on total current, not just real power.
How do power factor and motor efficiency differ when converting HP to Amps? Efficiency divides mechanical shaft watts (HP × 745.7) to get real input electrical watts; power factor divides real input watts to get apparent volt-amperes (VA), from which current is calculated.
Why does 3-phase power use the square root of 3 (1.732) instead of 3? Three phases deliver 3 × V_LN × I, and since line-to-line voltage is √3 times line-to-neutral voltage (V_LN = V_LL / √3), the expression simplifies to 3 / √3 = √3 × V_LL × I.