Temperature and bundling derating factors
NEC 310.15(B)(1) ambient temperature and 310.15(C)(1) conductor adjustment factors. Click any row to open it in the ampacity calculator.
NEC 310.15(B)(1) ambient temperature correction
| Ambient (°F) | Alternate (°C°F) | 60 °C factor |
75 °C factor |
90 °C factor |
Derated 90 °C (10 AWG Cu) |
Open in calculator |
|---|
No rows match that filter. Try a temperature like “40” or a factor like “0.80”.
NEC 310.15(C)(1) conductor bundling adjustment
| Current-carrying conductors | Adjustment factor | Percent of 310.16 | Derated 90 °C (10 AWG Cu) | Open in calculator |
|---|
How ambient and bundling derating work together
Start from the insulation column: Both ambient temperature correction and bundling adjustment multiply the conductor’s unadjusted Table 310.16 ampacity in its insulation rating column (for example, the 90 °C column for THHN or XHHW-2). Then check the terminal temperature limit per 110.14(C); the usable ampacity is the lower of the two.
Combined formula: I_adj = I_table(insulation) × f_temp × f_bundle. Equipment grounding conductors and normally non-current-carrying neutrals are excluded from the conductor count under 310.15(E) and (F).