Wire resistance and impedance

NEC Chapter 9 Table 8 DC resistance and Table 9 AC impedance at 75 °C (Ω per 1000 ftΩ per km). Click any row to open it in the wire size calculator.

Table 8 DC resistance & Table 9 AC impedance (75 °C, 60 Hz)

24 rows
Size Area (cmil) Table 8 DC R (Ω/1000 ft) Table 9 AC R (Ω/1000 ft) XL Effective Z (Cu) Open in calculator
Copper Aluminum Copper Aluminum

Table 8 and Table 9 calculation notes

DC vs. AC resistance: Table 8 gives coated or uncoated DC conductor resistance at 75 °C (using Class B stranded values for 14 through 8 AWG). Table 9 adds skin effect, proximity effect, and magnetic conduit eddy-current losses at 60 Hz for three single conductors in conduit.
Effective impedance formula: Z_eff = R × PF + X_L × sin(arccos(PF)). Sizes marked with * (700, 800, 900 kcmil) are interpolated by circular mils between adjacent Table 9 rows.
Temperature adjustment: Resistance varies with operating temperature: R_T = R_75 × [1 + α × (T − 75)], where α_Cu = 0.00323 / °C and α_Al = 0.00330 / °C at 75 °C.