Wire ampacity and derating calculator
Allowable NEC Table 310.16 ampacity after ambient temperature correction, raceway bundling adjustment, and 110.14(C) terminal check.
Conductor parameters
Loading NEC Table 310.16 data.
- Base 310.16 (90 °C)
- —
- Ambient factor (310.15(B))
- —
- Bundling factor (310.15(C))
- —
- Adjusted ampacity
- —
- Terminal limit (110.14(C))
- —
- Max breaker / OCPD
- —
Conductor cross-section and calculation working
- Conductor
- —
- Cross-sectional area
- —
- Insulated OD (THHN)
- —
- Stranding / bundle
- —
—
NEC ampacity derating methodology
Conductor ampacity in NFPA 70 (National Electrical Code) Table 310.16 assumes two baseline conditions: an ambient temperature of 30 °C (86 °F) and not more than three current-carrying conductors in a raceway, cable, or earth. Whenever an installation runs hotter, colder, or bundles four or more current-carrying conductors together, the installer must apply the correction and adjustment factors in NEC 310.15(B) and 310.15(C).
I_adjusted = I_table(insulation) × f_ambient × f_bundling
I_usable = min(I_adjusted, I_terminal(110.14(C)))
Why start from the 90 °C column? Modern building wire such as THHN, THWN-2, and XHHW-2 carries a 90 °C dry/wet insulation rating, even though panelboard lugs and molded-case circuit breakers are almost always rated for 60 °C or 75 °C terminations. NEC 110.14(C) allows you to take the higher 90 °C table ampacity as the starting point for ambient and bundling derating, provided the final usable ampacity does not exceed the conductor’s unadjusted ampacity in the terminal temperature column.
Three worked ampacity derating examples
Example 1: 10 AWG copper THHN in a warm rooftop conduit
Six current-carrying 10 AWG copper THHN (90 °C) conductors run inside an EMT conduit exposed to 40 °C (104 °F) ambient temperature, terminating on 75 °C rated breakers.
Base (310.16, 90 °C) = 40 A
Ambient factor (310.15(B)(1), 36–40 °C) = 0.91
Bundling factor (310.15(C)(1), 4–6 CCC) = 0.80
Adjusted ampacity = 40 × 0.91 × 0.80 = 29.1 A
75 °C terminal limit (110.14(C)) = 35 A
Usable ampacity = min(29.1, 35) = 29.1 A (25 A strict OCPD, or 30 A under 240.4(B)/(D))
Even though 10 AWG copper has a 30 A 240.4(D) cap and a 35 A 75 °C column rating, the combined 0.728 derating factor drops the conductor’s continuous thermal capacity to 29.1 A. If supplying general receptacles, step down to a 25 A breaker; for a single dedicated non-receptacle load, 240.4(B) allows rounding up to 30 A.
Example 2: 3/0 AWG copper XHHW-2 feeder in a 50 °C mechanical room
A 3-phase feeder uses four current-carrying 3/0 AWG copper XHHW-2 (90 °C) conductors (three phases plus a harmonic-rich neutral) routed through a 50 °C (122 °F) boiler room to 75 °C switchboard lugs.
Base (310.16, 90 °C) = 225 A
Ambient factor (310.15(B)(1), 46–50 °C) = 0.82
Bundling factor (310.15(C)(1), 4–6 CCC) = 0.80
Adjusted ampacity = 225 × 0.82 × 0.80 = 147.6 A
75 °C terminal limit (110.14(C)) = 200 A
Usable ampacity = 147.6 A (max 150 A OCPD per 240.4(B), or 125 A strict)
Because the boiler room drops adjusted ampacity to 147.6 A, a 200 A feeder breaker would overload the conductor. The circuit is capped at 147.6 A (allowing a 150 A breaker under 240.4(B) for a calculated load up to 147.6 A).
Example 3: 4 AWG aluminum THWN in a cool basement raceway
Nine current-carrying 4 AWG aluminum THWN (75 °C) conductors occupy a single PVC conduit in a 25 °C (77 °F) conditioned basement, landed on 75 °C panelboard lugs.
Base (310.16, 75 °C) = 65 A
Ambient factor (310.15(B)(1), 21–25 °C) = 1.05
Bundling factor (310.15(C)(1), 7–9 CCC) = 0.70
Adjusted ampacity = 65 × 1.05 × 0.70 = 47.8 A
75 °C terminal limit (110.14(C)) = 65 A
Usable ampacity = 47.8 A (45 A strict OCPD, or 50 A under 240.4(B))
Because 75 °C insulation was selected instead of 90 °C XHHW-2, the base starts at 65 A rather than 75 A, and the cold-ambient bonus of 1.05 only partially offsets the 0.70 bundling penalty.