Wirebench
AWG, ft, °Fmm², m, °C

Wire ampacity and derating calculator

Allowable NEC Table 310.16 ampacity after ambient temperature correction, raceway bundling adjustment, and 110.14(C) terminal check.

Conductor parameters

Conductor material
Insulation temperature rating
THHN, THWN-2, XHHW-2, XHH, RHH, USE-2
°F
30.0 °C (base 310.16)
CCC
1 to 3 current-carrying
Terminal limit (NEC 110.14(C))
Circuits 100 A or less default to 60 °C unless equipment is marked 75 °C.
Final usable ampacity Full table rating
— A

Loading NEC Table 310.16 data.

Base 310.16 (90 °C)
—
Ambient factor (310.15(B))
—
Bundling factor (310.15(C))
—
Adjusted ampacity
—
Terminal limit (110.14(C))
—
Max breaker / OCPD
—

Conductor cross-section and calculation working

Conductor
—
Cross-sectional area
—
Insulated OD (THHN)
—
Stranding / bundle
—
—

Advertisement

NEC ampacity derating methodology

Conductor ampacity in NFPA 70 (National Electrical Code) Table 310.16 assumes two baseline conditions: an ambient temperature of 30 °C (86 °F) and not more than three current-carrying conductors in a raceway, cable, or earth. Whenever an installation runs hotter, colder, or bundles four or more current-carrying conductors together, the installer must apply the correction and adjustment factors in NEC 310.15(B) and 310.15(C).

I_adjusted = I_table(insulation) × f_ambient × f_bundling I_usable = min(I_adjusted, I_terminal(110.14(C)))

Why start from the 90 °C column? Modern building wire such as THHN, THWN-2, and XHHW-2 carries a 90 °C dry/wet insulation rating, even though panelboard lugs and molded-case circuit breakers are almost always rated for 60 °C or 75 °C terminations. NEC 110.14(C) allows you to take the higher 90 °C table ampacity as the starting point for ambient and bundling derating, provided the final usable ampacity does not exceed the conductor’s unadjusted ampacity in the terminal temperature column.

Equipment grounding and neutral rules: Under NEC 310.15(E) and 310.15(F), equipment grounding conductors never count toward the raceway bundling total. A grounded neutral conductor counts only when it carries only the unbalanced current of a 3-wire circuit derived from a 4-wire wye system (such as 208Y/120 V two-pole plus neutral), or when more than 50% of a 3-phase 4-wire wye feeder supplies nonlinear harmonic loads.
Small-conductor OCPD limits (NEC 240.4(D)): Overcurrent protection for 14, 12, and 10 AWG conductors cannot exceed 15 A, 20 A, and 30 A for copper (or 15 A and 25 A for 12 and 10 AWG aluminum) unless covered by specific exceptions such as motor branch circuits (Article 430) or HVAC equipment (Article 440). For 8 AWG and larger conductors where standard breaker ratings do not match the adjusted ampacity, NEC 240.4(B) permits the next higher standard rating up to 800 A if the circuit does not supply multioutlet branch receptacles.

Three worked ampacity derating examples

Example 1: 10 AWG copper THHN in a warm rooftop conduit

Six current-carrying 10 AWG copper THHN (90 °C) conductors run inside an EMT conduit exposed to 40 °C (104 °F) ambient temperature, terminating on 75 °C rated breakers.

Base (310.16, 90 °C) = 40 A Ambient factor (310.15(B)(1), 36–40 °C) = 0.91 Bundling factor (310.15(C)(1), 4–6 CCC) = 0.80 Adjusted ampacity = 40 × 0.91 × 0.80 = 29.1 A 75 °C terminal limit (110.14(C)) = 35 A Usable ampacity = min(29.1, 35) = 29.1 A (25 A strict OCPD, or 30 A under 240.4(B)/(D))

Even though 10 AWG copper has a 30 A 240.4(D) cap and a 35 A 75 °C column rating, the combined 0.728 derating factor drops the conductor’s continuous thermal capacity to 29.1 A. If supplying general receptacles, step down to a 25 A breaker; for a single dedicated non-receptacle load, 240.4(B) allows rounding up to 30 A.

Example 2: 3/0 AWG copper XHHW-2 feeder in a 50 °C mechanical room

A 3-phase feeder uses four current-carrying 3/0 AWG copper XHHW-2 (90 °C) conductors (three phases plus a harmonic-rich neutral) routed through a 50 °C (122 °F) boiler room to 75 °C switchboard lugs.

Base (310.16, 90 °C) = 225 A Ambient factor (310.15(B)(1), 46–50 °C) = 0.82 Bundling factor (310.15(C)(1), 4–6 CCC) = 0.80 Adjusted ampacity = 225 × 0.82 × 0.80 = 147.6 A 75 °C terminal limit (110.14(C)) = 200 A Usable ampacity = 147.6 A (max 150 A OCPD per 240.4(B), or 125 A strict)

Because the boiler room drops adjusted ampacity to 147.6 A, a 200 A feeder breaker would overload the conductor. The circuit is capped at 147.6 A (allowing a 150 A breaker under 240.4(B) for a calculated load up to 147.6 A).

Example 3: 4 AWG aluminum THWN in a cool basement raceway

Nine current-carrying 4 AWG aluminum THWN (75 °C) conductors occupy a single PVC conduit in a 25 °C (77 °F) conditioned basement, landed on 75 °C panelboard lugs.

Base (310.16, 75 °C) = 65 A Ambient factor (310.15(B)(1), 21–25 °C) = 1.05 Bundling factor (310.15(C)(1), 7–9 CCC) = 0.70 Adjusted ampacity = 65 × 1.05 × 0.70 = 47.8 A 75 °C terminal limit (110.14(C)) = 65 A Usable ampacity = 47.8 A (45 A strict OCPD, or 50 A under 240.4(B))

Because 75 °C insulation was selected instead of 90 °C XHHW-2, the base starts at 65 A rather than 75 A, and the cold-ambient bonus of 1.05 only partially offsets the 0.70 bundling penalty.

Frequently asked questions

Which NEC Table 310.16 temperature column do I start from when derating THHN wire? Start from the 90 °C column for THHN, THWN-2, or XHHW-2 when applying 310.15(B) ambient and 310.15(C) bundling factors, then cap the result at the 60 °C or 75 °C terminal rating per NEC 110.14(C).
How do equipment grounding conductors and neutrals affect the bundling count? Equipment grounding conductors never count. Neutrals count only when carrying unbalanced current of a 3-wire circuit from a 4-wire wye system, or when nonlinear loads exceed 50% on a 3-phase 4-wire wye circuit.
Does NEC 240.4(D) override higher 90 °C ampacity on 14, 12, and 10 AWG copper wire? Yes for general branch circuits: overcurrent devices are capped at 15 A (14 AWG Cu), 20 A (12 AWG Cu / 15 A Al), and 30 A (10 AWG Cu / 25 A Al), even though derating still begins from the 90 °C column.

Related calculators and reference charts

Usable ampacity —
No result View