Wirebench
AWG, ft, °Fmm², m, °C

Breaker size calculator

Standard NEC 240.6(A) breaker or fuse rating, 125% continuous load factor, minimum conductor & EGC sizes, and GFCI/AFCI requirements.

Load and circuit details

A
V
PF
Unity (1.00)
Phase
Duty cycle (NEC 210.20 / 215.3)
Runs 3 hours or more continuously
Conductor material
Terminal rating
Recommended overcurrent device (NEC 240.6(A)) No result
— A

Enter load, voltage, and duty cycle to size the circuit breaker.

Required OCPD ampacity
—
Min copper wire
—
Min aluminum wire
—
Cu EGC (250.122)
—
Al EGC (250.122)
—
Load utilization
—

GFCI / AFCI protection and standard breaker table

GFCI protection (NEC 210.8) —

Select a room location to evaluate GFCI rules.

AFCI protection (NEC 210.12) —

Select a room location to evaluate AFCI rules.

Breaker (240.6) Max cont. load (80%) Min Cu wire Min Al wire Cu EGC (250.122) Al EGC (250.122)
—

IEC mode converts wire and EGC sizes to metric mm² using conservative NEC Table 310.16 and Table 250.122 equivalents; OCPD ratings follow NEC 240.6(A) standard steps.

Advertisement

NEC circuit breaker, wire, and protection sizing rules

Overcurrent protective devices (circuit breakers and fuses) protect conductors from overheating under overload and short-circuit faults. Under NEC 210.20(A) and 215.3, noncontinuous loads are sized at 100%, while continuous loads (operating for 3 hours or more) require multiplying by 125% before choosing the next standard rating in NEC 240.6(A).

I_load = Watts / (V × K_phase × PF) [K_phase = 1 for 1-ph/DC, √3 for 3-ph] I_required = I_load × (1.25 if continuous else 1.00) OCPD_rating = smallest NEC 240.6(A) standard rating ≥ I_required
Small conductors and terminal limits: NEC 240.4(D) limits overcurrent protection to 15 A for 14 AWG copper, 20 A for 12 AWG copper (15 A Al), and 30 A for 10 AWG copper (25 A Al) on general branch circuits. Equipment terminations rated 100 A or less default to the 60 °C column of Table 310.16 unless both the breaker and equipment lugs are marked 75 °C per NEC 110.14(C).
Note on motor and HVAC equipment: Dedicated motor circuits (NEC Article 430) and hermetic refrigerant motor-compressors (NEC Article 440) use locked-rotor, full-load-current tables, and nameplate MOCP/MCA values rather than the general 125% rule.

Three worked breaker and fuse sizing examples

Example 1: 1,920 W commercial kitchen appliance at 120 V continuous

A 1,920 W warming cabinet runs continuously (≥ 3 hours) on a 120 V single-phase kitchen branch circuit with 75 °C terminals.

I_load = 1920 W / 120 V = 16.0 A I_required = 16.0 A × 1.25 = 20.0 A NEC 240.6(A) breaker = 20 A (1-pole) Min wire: 12 AWG Cu (20 A 240.4(D) cap), EGC = 12 AWG Cu (Table 250.122)

In a dwelling kitchen, NEC 210.8(A)(6) requires GFCI and NEC 210.12(A) requires AFCI on this 120 V 20 A circuit, pointing to a 1-pole Dual-Function AFCI/GFCI breaker.

Example 2: 7,680 W (32 A) Level 2 EV charger in a garage at 240 V continuous

A 32 A (7,680 W) Level 2 EVSE is a continuous load by NEC 625.41, installed in a residential garage at 240 V single-phase.

I_load = 32.0 A I_required = 32.0 A × 1.25 = 40.0 A NEC 240.6(A) breaker = 40 A (2-pole) Min wire (75 °C): 8 AWG Cu (50 A) or 6 AWG Al (50 A), EGC = 10 AWG Cu (8 AWG Al)

If connected via a 240 V receptacle in a garage, NEC 210.8(A)(2) and 625.54 require a 2-pole GFCI breaker. AFCI is not required on 240 V 40 A circuits.

Example 3: 45 kW 480 V 3-phase electric duct heater (non-continuous or continuous)

A 45,000 W 480 V 3-phase heater (PF = 1.00) treated as a continuous load with 75 °C lugs:

I_load = 45,000 / (480 × √3) = 54.13 A I_required = 54.13 A × 1.25 = 67.66 A Next standard NEC 240.6(A) OCPD = 70 A (3-pole) Min wire (75 °C): 4 AWG Cu (85 A) or 3 AWG Al (75 A), EGC = 8 AWG Cu (6 AWG Al)

67.66 A rounds up to a 70 A 3-pole breaker under NEC 240.6(A), paired with a 8 AWG copper equipment grounding conductor from Table 250.122 (for 61–100 A OCPD).

Frequently asked questions

How does the NEC 125% continuous load rule affect breaker sizing? Continuous loads running 3 hours or more require sizing standard overcurrent devices to at least 125% of the continuous current (keeping actual continuous load at or below 80% of breaker rating).
What are the standard NEC 240.6(A) circuit breaker and fuse ratings? Standard ratings are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A, and up to 6000 A.
When are GFCI and AFCI breakers both required on the same circuit? Dwelling kitchens and laundry areas on 120 V single-phase 15 A or 20 A circuits require both GFCI (NEC 210.8(A)) and AFCI (NEC 210.12(A)) protection, typically using a dual-function breaker.