DC battery and inverter cable calculator
Size 12 V, 24 V, and 48 V battery-to-inverter and RV/marine/van DC cables from inverter wattage or DC amps, round-trip length, and 2%–3% drop limits, with Class T/ANL fuse sizing.
DC bank and load parameters
Enter system voltage, inverter watts or DC amps, and round-trip cable length.
- DC load current
- —
- 125% design current
- —
- Recommended fuse
- —
- Round-trip voltage drop
- —
- Voltage at inverter
- —
- Cable power loss
- —
4 AWG through 4/0 AWG cable comparison
| Cable size (Cu) | 75 °C NEC | 90 °C adj. | Drop % | Volts lost | Power lost | Assessment |
|---|
IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance at 75 °C for DC voltage drop.
Sizing 12 V, 24 V, and 48 V DC battery and inverter cables
Low-voltage DC circuits carry dramatically higher current per kilowatt than 120 V or 240 V AC circuits, and even a half-volt drop in a 12 V bank can trigger an inverter low-voltage alarm under heavy surge loads.
Inverter DC current: I_dc = P_ac / (V_dc × η_inv)
Continuous design current: I_design = I_dc × 1.25
Round-trip voltage drop: V_drop = I_dc × R_75C_per_kft × (L_roundtrip / 1000) / N_parallel
Percent drop: %VD = (V_drop / V_dc) × 100 ≤ 2% (inverter) or 3% (general DC)
Why 4 AWG through 4/0 AWG dominates battery wiring: Small DC loads use 10 AWG to 6 AWG, while battery-to-inverter and DC busbar trunks almost always land between 4 AWG and 4/0 AWG fine-stranded copper (such as UL 1426 marine tinned copper or NEC RHH/RHW-2 / welding cable rated for battery lugs). When continuous 125% current exceeds a single 4/0 AWG conductor's 230 A (75 °C terminal) rating—typical on 3000 W+ 12 V inverters—install two matched parallel cables per pole (such as 2 × 2/0 AWG or 2 × 4/0 AWG) of identical length and crimp lug termination per NEC 310.10(G).
Class T vs. ANL fuse selection: Always place the main battery fuse as close as practical to the positive battery post (within 7 inches in marine ABYC E-11, or 18 inches in RV/automotive). LiFePO4 battery packs can deliver 5,000–20,000 A into a short circuit; always use a Class T fuse (20,000 A AIC) on LiFePO4 and 48 V systems, while ANL or Mega fuses are suitable for 12 V / 24 V AGM and flooded lead-acid auxiliary circuits.
12 V / 24 V / 48 V Inverter cable & fuse quick reference (10 ft round-trip, 85% eff.)
| System | Inverter W | DC draw | 125% design | Fuse (240.6) | Copper cable (75 °C) | Drop (10 ft RT) |
|---|
Three worked DC battery and inverter cable examples
Example 1: 12 V 2000 W camper van inverter, 10 ft round-trip (LiFePO4)
A 2000 W pure-sine inverter (85% efficiency) sits 5 ft one-way (10 ft round-trip positive + negative) from a 12 V LiFePO4 battery bank under a 2% maximum voltage drop target.
DC current = 2000 W / (12 V × 0.85) = 196.1 A
125% design current = 196.1 A × 1.25 = 245.1 A → 250 A Class T fuse
75 °C Cu NEC 310.16: 2 × 1/0 AWG parallel = 300 A (0.96% drop, 0.12 V lost); single 4/0 AWG = 230 A @ 75 °C (260 A @ 90 °C)
4/0 AWG Cu drop (10 ft RT): 196.1 A × 0.0608 × 0.010 = 0.119 V (0.99% ≤ 2%, pass)
Under strict NEC 75 °C terminal limits (245.1 A required > 230 A of single 4/0), the calculator selects 2 × 1/0 AWG copper parallel sets (300 A capacity, 0.96% drop / 0.12 V lost), while in 90 °C / 105 °C free-air marine/RV battery service a single 4/0 AWG copper cable (260 A+, 0.99% drop) is also commonly used with a 250 A Class T fuse at the LiFePO4 positive terminal.
Example 2: 24 V 3000 W off-grid cabin inverter, 12 ft round-trip
Stepping up to 24 V doubles voltage and halves DC current for a 3000 W inverter (85% efficiency) located 6 ft from the battery bank (12 ft round-trip).
DC current = 3000 W / (24 V × 0.85) = 147.1 A
125% design current = 147.1 A × 1.25 = 183.8 A → 200 A Class T fuse
75 °C Cu NEC 310.16: 3/0 AWG Cu = 200 A (passes 183.8 A & 200 A fuse)
3/0 AWG Cu drop (12 ft RT): 147.1 A × 0.0766 × 0.012 = 0.135 V (0.56% ≤ 2%)
Use 3/0 AWG copper with a 200 A Class T fuse—easily fitting single-cable lugs with only 0.56% voltage drop (0.14 V).
Example 3: 12 V 80 A DC fridge/heater/lights trunk, 30 ft round-trip (3% drop)
A marine/RV auxiliary DC distribution panel draws up to 80 A at 12 V and is mounted 15 ft forward of the AGM battery bank (30 ft round-trip) with a strict 3% (0.36 V) drop limit.
125% design current = 80 A × 1.25 = 100.0 A → 100 A ANL or Class T fuse
Ampacity minimum (75 °C): 3 AWG Cu = 100 A (or 2 AWG Cu = 115 A)
Drop on 3 AWG (30 ft RT): 80 A × 0.245 × 0.030 = 0.588 V (4.90% > 3%, FAIL!)
Drop on 1 AWG (30 ft RT): 80 A × 0.154 × 0.030 = 0.370 V (3.08% > 3%, FAIL!)
Drop on 1/0 AWG (30 ft RT): 80 A × 0.122 × 0.030 = 0.293 V (2.44% ≤ 3%, PASS!)
Even though 3 AWG carries 100 A thermally, the 30 ft round-trip at 12 V forces upsizing three sizes to 1/0 AWG copper (or 2/0 AWG for < 2% drop) protected by a 100 A ANL or Class T fuse.