EV charger wire and breaker calculator
Size Level 2 EVSE circuits per NEC 625.41 125% continuous load, 75 °C terminal limits, voltage drop, and copper vs. aluminum feeder comparison.
EVSE circuit parameters
Select an EVSE preset or enter charging current and distance.
- 125% design load (625.41)
- —
- Breaker rating (240.6)
- —
- Cu voltage drop
- —
- Al feeder drop
- —
- Cu / Al EGC (250.122)
- —
- Charging power / range
- —
Materials take-off and compliance checks
| Line item | Copper option | Aluminum feeder option | Qty / Length |
|---|
IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance adjusted to 75 °C for voltage drop.
NEC 625.41 EVSE sizing, 75 °C terminals, and Cu vs. Al feeders
Under NEC 625.41, electric vehicle supply equipment (EVSE) is classified as a continuous load because charging sessions routinely run three hours or longer at full rated current. Both the branch-circuit conductors and the overcurrent protective device must have a rating of at least 125% of the charger's maximum output current.
I_required = I_EVSE × 1.25 (NEC 625.41)
OCPD_min = next standard NEC 240.6(A) breaker ≥ I_required
Ampacity check: min(I_adjusted_insul, I_terminal_75C) ≥ I_required (110.14(C))
Voltage drop (actual load): %VD = (2 × I_EVSE × R × L / 1000) / V_system × 100
75 °C terminal rating rule (NEC 110.14(C)): Even when pulling 90 °C THHN/THWN-2 or XHHW-2 wire, equipment breaker and EVSE terminals are listed at 75 °C (60 °C for NM-B under NEC 334.80). The 90 °C column may be used for ambient derating, but the final unadjusted ampacity cannot exceed the 75 °C column (or 60 °C for NM-B). That is why 6 AWG Cu THHN (65 A at 75 °C) is valid for a 48 A / 60 A circuit, while 6 AWG Cu NM-B (55 A at 60 °C) is not.
Copper vs. aluminum feeders (NEC 110.14): Virtually all Level 2 EVSE wall connectors have copper-only lugs. To save cost on long runs, run an aluminum SER or XHHW-2 feeder (typically two AWG sizes larger than copper) to a disconnect, subpanel, or junction box with dual-rated Al9Cu splice lugs (such as Polaris connectors) and finish the final whip to the EVSE in copper.
Level 2 EV charger quick reference (240 V, up to 50 ft)
| EVSE current | Power (240 V) | 125% min (625.41) | Breaker (240.6) | Cu THHN (75 °C) | Cu NM-B (60 °C) | Al feeder (75 °C) | Cu EGC (250.122) |
|---|
Three worked EV charger sizing examples
Example 1: 48 A hardwired charger at 240 V, 50 ft (60 A breaker)
A 48 A wall connector (11.5 kW) is hardwired 50 ft from the main panel in EMT conduit at 30 °C ambient using 90 °C THHN conductors on 75 °C breaker lugs.
Design current = 48 A × 1.25 = 60.0 A → 60 A 2-pole breaker
Copper THHN (75 °C): 6 AWG Cu = 65 A ≥ 60 A (NM-B 6 AWG is only 55 A, fails)
Copper voltage drop: 2 × 48 × 0.491 × 0.050 / 240 = 0.98% (≤ 3%)
Aluminum feeder (75 °C): 4 AWG Al = 65 A ≥ 60 A, drop = 1.02%
EGC (Table 250.122 for 60 A): 10 AWG Cu (or 8 AWG Al feeder ground)
Use two 6 AWG Cu THHN conductors plus one 10 AWG Cu EGC in 3/4" EMT, or run 4-4-4-6 SER aluminum feeder to a garage disconnect/junction box and transition to a 6 AWG Cu whip.
Example 2: 40 A NEMA 14-50 receptacle setup at 240 V, 60 ft (50 A GFCI)
A plug-in EVSE set to 40 A (9.6 kW) uses a heavy-duty NEMA 14-50 receptacle in a detached garage 60 ft from the panel, wired in 75 °C THHN/THWN-2.
Design current = 40 A × 1.25 = 50.0 A → 50 A 2-pole GFCI breaker (NEC 625.54)
75 °C Cu ampacity: 8 AWG Cu = 50 A (passes 50 A); 6 AWG Cu = 65 A (common upgrade)
8 AWG Cu voltage drop: 2 × 40 × 0.778 × 0.060 / 240 = 1.56% (≤ 3%)
Conductors for NEMA 14-50: 2 Hots + 1 Neutral (all 8 AWG Cu) + 10 AWG Cu EGC
Even though the EVSE draws zero neutral current at 240 V, a NEMA 14-50 receptacle must have a full-size neutral conductor installed so a future 120/240 V appliance is properly served. Use an EV-rated heavy-duty 14-50 receptacle and a 50 A GFCI breaker per NEC 625.54.
Example 3: 80 A commercial/fleet hardwired EVSE at 240 V, 180 ft (100 A breaker)
An 80 A hardwired charger (19.2 kW) is located 180 ft from the main distribution panel in a commercial parking bay with a 3% maximum voltage drop budget.
Design current = 80 A × 1.25 = 100.0 A → 100 A 2-pole breaker
75 °C Cu ampacity min: 3 AWG Cu = 100 A (drop = 2 × 80 × 0.245 × 0.180 / 240 = 2.94% ≤ 3%)
75 °C Al feeder min: 1 AWG Al = 100 A (drop = 2 × 80 × 0.253 × 0.180 / 240 = 3.04% > 3%)
Upsized Al for ≤ 3% drop: 1/0 AWG Al (drop = 2.41%)
EGC (250.122 for 100 A): 8 AWG Cu (or 6 AWG Al upsized to 4 AWG Al per 250.122(B))
At 180 ft, 3 AWG copper stays just inside the 3% limit, whereas 1 AWG aluminum hits 3.04% and steps up to 1/0 AWG aluminum feeder ending at a 100 A disconnect with a short 3 AWG copper whip to the EVSE.