Transformer primary and secondary wire and OCPD calculator
Size 1-phase and 3-phase dry-type transformers from 3 kVA to 500 kVA using NEC Table 450.3(B) overcurrent limits and primary/secondary conductor ratings.
Transformer parameters
Select kVA, primary/secondary voltages, and protection scheme.
- Primary FLA
- —
- Max primary OCPD (450.3)
- —
- Secondary FLA
- —
- Max secondary OCPD
- —
- Primary EGC (250.122)
- —
- Sec. GEC / SSBJ (250.30)
- —
Complete transformer feeder & OCPD schedule
| Circuit item | Rating / Size | Ampacity / Limit | NEC reference |
|---|
IEC mode maps selected AWG/kcmil conductors to equivalent IEC 60228 cross-sections while maintaining NEC Table 310.16 ampacity.
NEC Table 450.3(B) transformer sizing rules (1000 V or less)
Dry-type transformer overcurrent protection (OCPD) follows NEC 450.3(B), while primary and secondary feeder conductors are governed separately by NEC 240.4 and 240.21(C). Grounding and bonding of the separately derived secondary system follow NEC 250.30.
1-phase FLA: I = (kVA × 1000) / V
3-phase FLA: I = (kVA × 1000) / (V × √3)
Primary-Only OCPD: 125% FLA (Note 1 next std if ≥ 9 A) | 167% (< 9 A, no Note 1) | 300% (< 2 A)
Primary + Secondary OCPD: Primary ≤ 250% FLA (no Note 1); Secondary ≤ 125% (Note 1 if ≥ 9 A) or 167% (< 9 A)
Transformer protection vs. conductor protection: Table 450.3(B) allows up to a 250% primary OCPD when the secondary is also protected, so magnetizing inrush (typically 8×–12× FLA for a few cycles) will not trip the primary breaker. However, NEC 240.4 still requires the primary feeder conductors to be protected at their ampacity by that primary breaker (unless using a 240.21(B) feeder tap). Setting the primary breaker at 125%–150% keeps wire size compact while still allowing standard transformer energizing.
Quick reference: 3-phase 480 V → 208 V transformers (3 to 500 kVA)
| kVA | Pri FLA | Pri 125% max | Pri 250% max | Sec FLA | Sec 125% max | Sec Cu (75 °C) |
|---|
Three worked transformer sizing examples
Example 1: 45 kVA 3-phase 480 V delta to 208Y/120 V panel transformer
A 45 kVA 3-phase dry-type transformer feeds a 208Y/120 V subpanel from a 480 V distribution panel using copper THHN at 75 °C terminals.
Primary FLA = 45,000 / (480 × √3) = 54.1 A
Secondary FLA = 45,000 / (208 × √3) = 124.9 A
Table 450.3(B) Pri+Sec limits:
Primary max (250%) = 2.50 × 54.1 = 135.3 A → 125 A max (no Note 1)
Primary 125% standard = 1.25 × 54.1 = 67.7 A → 70 A breaker + 4 AWG Cu (85 A)
Secondary max (125% + Note 1) = 1.25 × 124.9 = 156.1 A → 175 A breaker + 2/0 Cu (175 A)
With a 70 A primary breaker and 4 AWG copper primary conductors, plus a 175 A secondary main breaker and 2/0 AWG copper secondary conductors (with 4 AWG Cu GEC/SSBJ per Table 250.66 / 250.102), every NEC 450.3 and 240.21(C) check passes.
Example 2: 15 kVA 1-phase 480 V to 120/240 V control/lighting transformer
A 15 kVA single-phase transformer steps 480 V down to 120/240 V 3-wire for shop lighting and receptacles.
Primary FLA = 15,000 / 480 = 31.25 A (≥ 9 A)
Secondary FLA = 15,000 / 240 = 62.5 A (≥ 9 A)
Primary 125% = 1.25 × 31.25 = 39.1 A → 40 A 2-pole breaker + 8 AWG Cu (50 A)
Secondary 125% = 1.25 × 62.5 = 78.1 A → 80 A 2-pole main + 4 AWG Cu (85 A)
Because the secondary is 3-wire 120/240 V, NEC 240.21(C) requires secondary overcurrent protection (80 A) even though the primary OCPD is at 125% (40 A).
Example 3: 300 kVA 3-phase 480 V to 208Y/120 V service transformer (parallel sets)
A 300 kVA transformer supplies a large 208Y/120 V main switchboard using copper THHN conductors capped at 500 kcmil per parallel set.
Primary FLA = 300,000 / (480 × √3) = 360.8 A → 125% = 451.1 A → 500 A breaker (Note 1)
Primary wire (2 parallel sets): 2 × 250 kcmil Cu (2 × 255 A = 510 A ≥ 500 A)
Secondary FLA = 300,000 / (208 × √3) = 832.7 A → 125% = 1040.9 A → 1200 A main (Note 1)
Secondary wire (4 parallel sets): 4 × 350 kcmil Cu (4 × 310 A = 1240 A ≥ 1200 A)
or 3 parallel sets of 600 kcmil Cu (3 × 420 A = 1260 A)
Sizing parallel sets automatically keeps cable pulling manageable while providing the full 1200 A secondary ampacity and Table 250.102(C)(1) 3/0 AWG copper supply-side bonding jumper.