Electric motor wire and breaker calculator

Lookup NEC Table 430.248 (1-phase) and Table 430.250 (3-phase) FLC from 1/2 HP to 200 HP, size 125% conductors (430.22), and inverse-time breakers up to 250% (430.52).

Motor and circuit parameters

Common motor presets
Motor phase
NEC Table 430.250
Table voltage rating
A
Used for 430.32 overload only
Material
Terminal rating
°F
CCC
ft
%
Minimum branch conductor & breaker (NEC 430.22 / 430.52) No result
— Copper THHN

Select motor horsepower, voltage, and run length to compute conductor and OCPD sizes.

NEC Table FLC
—
Min wire ampacity (125%)
—
Max branch OCPD (430.52)
—
Max overload relay (430.32)
—
Running voltage drop
—
EGC / Min conduit
—

NEC 430.52 protective device limits & bill of materials

NEC 240.4(G) motor circuit rule: Motor branch-circuit conductors are sized at 125% of Table FLC (NEC 430.22) and protected from overloads by the motor starter/overload relay (NEC 430.32). The general small-conductor caps in 240.4(D) do not restrict the branch-circuit breaker or fuse selected under Table 430.52.

NEC Table 430.52 device Max % FLC Calculated Max std rating EGC (250.122)
Component Specification Code basis

IEC mode selects the smallest metric cross-section whose conservative AWG equivalent satisfies the NEC 430.22 125% FLC ampacity and computes voltage drop using IEC 60228 resistance.

Advertisement

NEC Article 430 motor branch-circuit sizing method

Sizing an electric motor branch circuit separates thermal overload protection from high-inrush short-circuit protection. All conductor and breaker limits start from the NEC Table Full-Load Current (FLC), not the motor nameplate current.

1. Lookup Table FLC: NEC Table 430.248 (1-phase) or Table 430.250 (3-phase) 2. Branch conductors (NEC 430.22): I_cond_min = 1.25 × FLC (checked at 75 °C terminals & 90 °C derated) 3. Branch OCPD max (NEC 430.52): Inverse-time breaker = 250% × FLC (round up to next std 240.6(A) size per Exc. 1) Dual-element fuse = 175% × FLC | Non-time-delay fuse = 300% × FLC | MCP = 800% × FLC 4. Overload relay max (NEC 430.32): 125% × Nameplate FLA (SF ≥ 1.15 or ≤ 40 °C), else 115% × FLA

110.14(C) termination rule: Motors rated over 100 A or circuits over 100 A use the 75 °C ampacity column in NEC Table 310.16. Even when using 90 °C THHN conductors, ambient temperature correction and bundling derating start from the 90 °C column, while final conductor termination ampacity cannot exceed the 75 °C (or 60 °C for ≤ 100 A equipment with 60 °C lugs) column.

NEC Table 430.250 full-load current reference (3-phase)

Three worked motor circuit examples

Example 1: 5 HP, 230 V, 1-phase shop air compressor (75 ft)

A 5 HP single-phase 230 V motor has a nameplate FLA of 26.0 A (SF 1.15) and is fed 75 ft in 3/4" EMT with 90 °C copper THHN on 75 °C terminals.

NEC Table 430.248 FLC (5 HP, 230 V, 1-phase) = 28.0 A NEC 430.22 min conductor ampacity = 1.25 × 28.0 A = 35.0 A → 10 AWG Cu (35 A at 75 °C) NEC 430.52 inverse-time breaker max = 2.50 × 28.0 A = 70 A (exact standard rating) NEC 430.32 overload max = 1.25 × 26.0 A nameplate = 32.5 A Voltage drop (10 AWG Cu, 75 ft): 2 × 28 × 1.24 × 0.075 / 230 = 2.26% (≤ 3%, pass)

10 AWG copper with an 8 AWG copper EGC (sized from the 70 A breaker per Table 250.122) in 1/2" EMT satisfies all NEC Article 430 requirements. Note that 10 AWG is allowed on a 70 A motor breaker under NEC 240.4(G).

Example 2: 10 HP, 460 V, 3-phase industrial lathe (75 ft)

A 10 HP, 460 V, 3-phase induction motor runs 75 ft in EMT using 75 °C copper terminals at 86 °F (30 °C) ambient.

NEC Table 430.250 FLC (10 HP, 460 V, 3-phase) = 14.0 A NEC 430.22 min conductor ampacity = 1.25 × 14.0 A = 17.5 A → 14 AWG Cu (20 A at 75 °C) NEC 430.52 inverse-time breaker max = 2.50 × 14.0 A = 35 A (or 1.75 × 14 = 24.5 → 25 A dual-element fuse) Voltage drop (14 AWG Cu, 75 ft): √3 × 14 × 3.14 × 0.075 / 460 = 1.24% (≤ 3%, pass)

14 AWG copper with a 35 A 3-pole inverse-time breaker and 10 AWG copper EGC (Table 250.122 for 35 A) in 1/2" EMT is code-compliant. Many industrial plants specify 12 AWG minimum for mechanical robustness.

Example 3: 50 HP, 208 V, 3-phase chiller pump (180 ft run, 3/0 AWG Cu)

A 50 HP, 208 V, 3-phase pump sits 180 ft from the motor control center in 86 °F (30 °C) ambient with a 3% running voltage drop target.

NEC Table 430.250 FLC (50 HP, 208 V, 3-phase) = 143 A NEC 430.22 min conductor ampacity = 1.25 × 143 A = 178.8 A → 3/0 AWG Cu (200 A at 75 °C) Voltage drop at 3/0 Cu (180 ft, Table 9 Z_eff @ 0.85 PF): 1.89% in PVC (0.088 Ω/kft) | 2.02% in steel EMT (0.095 Ω/kft) NEC 430.52 inverse-time breaker max = 2.50 × 143 A = 357.5 A → 400 A breaker (Exception 1 next standard)

3/0 AWG copper satisfies both the 178.8 A ampacity requirement and keeps running voltage drop at 1.89% in PVC (2.02% in steel EMT, both well under 3%), protected by up to a 400 A inverse-time breaker and a 3 AWG copper EGC in 2" EMT.

Frequently asked questions

Why do NEC motor calculations use Table 430.248 and Table 430.250 instead of motor nameplate amps? NEC 430.6(A)(1) mandates Table FLC values for wire and branch OCPD sizing so circuits remain adequate across motor replacements. Nameplate FLA is used only for setting motor overload protection under NEC 430.32.
Why can a motor circuit use a 250% breaker on wire that is smaller than the breaker rating? NEC 240.4(G) exempts motors from 240.4(D) and general 240.4 conductor-ampacity rules. The 250% breaker handles short circuits and ground faults during high-inrush starts, while the overload relay protects the 125% FLC conductors against sustained overloads.
Can I round up to the next standard breaker size under NEC 430.52? Yes. NEC 430.52(C)(1) Exception No. 1 allows selecting the next higher standard NEC 240.6(A) rating when the calculated percentage (such as 250% × FLC) falls between standard breaker sizes.

Related calculators and reference charts

Motor wire / OCPD —