Wirebench
AWG, ft, °Fmm², m, °C

Submersible well pump wire size calculator

Size 1/2 HP to 5 HP submersible pump cables (2-wire or 3-wire with control box) across combined trench run and well depth under strict voltage drop limits.

Well pump & run parameters

Motor horsepower (1-phase submersible)
Pump voltage
A
NEC 430.248: 8.0 A; SFA: 9.8 A
Down-well motor wiring
3 power wires (Blk/Red/Yel) + green EGC from control box to pump.
ft
ft
Strict voltage drop limit
%
Minimum copper pump cable size No result
— Copper submersible

Select motor horsepower, trench run, and vertical well depth.

Trench run—
Well depth—
Combined run—
Voltage drop
—
Voltage at motor
—
Max length at this size
—
125% NEC 430.22
—
Breaker (NEC 430.52)
—
EGC (250.122 / 250.122(B))
—

Materials take-off list

Segment / item Cable / hardware specification Qty / Length

IEC mode uses conservative AWG equivalents from NEC Table 310.16 for ampacity and IEC 60228 resistance adjusted to 75 °C for voltage drop.

Advertisement

How submersible well pump wire is sized under NEC Article 430

Submersible well pumps almost always hit voltage drop limits long before thermal ampacity limits because the circuit combines an outdoor buried trench run with a vertical drop down the borehole.

L_total = L_trench + L_well_depth I_ampacity = 1.25 × max(I_FLC_430.248, I_SFA_nameplate) (NEC 430.22) %VD = (2 × I_SFA × R_75C × L_total / 1000) / V_system × 100 ≤ 3%

2-wire vs. 3-wire with control box: A 2-wire submersible motor contains an internal start switch and runs on two power conductors plus an insulated green EGC (1/2 HP to 1-1/2 HP). A 3-wire submersible motor places the start capacitor and potential relay in an above-ground control box; the trench run from the pressure switch to the control box still uses 2 power conductors plus EGC, while the down-well submersible cable uses 3 power conductors (Black, Red, Yellow) plus green EGC.

NEC 250.122(B) ground upsizing warning: Whenever you step up the power conductors for voltage drop (for example, from 12 AWG code minimum to 8 AWG), NEC 250.122(B) requires increasing the equipment grounding conductor proportionally by circular mil area. Factory flat submersible cables often mold a smaller ground wire (such as 10 AWG ground inside 8/3 w/G); if 250.122(B) requires a full-size EGC, install individual THW/XHHW submersible conductors with a compliant green copper ground.

Maximum combined run length (ft) at 3% drop, 75 °C Copper

Pump rating NEC FLC / SFA Breaker (430.52) 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG

Three worked submersible well pump examples

Example 1: 1 HP 230 V 3-wire pump, 120 ft trench + 200 ft well depth

A 1 HP 230 V 3-wire submersible pump (8.0 A NEC 430.248 FLC, 9.8 A max SFA) sits 200 ft down a borehole fed by a 120 ft trench from the house pressure tank, under a 3% drop limit.

Combined one-way length = 120 ft + 200 ft = 320 ft NEC 430.22 ampacity = 9.8 A × 1.25 = 12.3 A (14/12 AWG Cu thermal min; 20 A breaker) 12 AWG Cu drop = 2 × 9.8 × 1.98 × 0.320 / 230 = 5.40% (> 3%, fail) 10 AWG Cu drop = 2 × 9.8 × 1.24 × 0.320 / 230 = 3.38% (> 3%, fail) 8 AWG Cu drop = 2 × 9.8 × 0.778 × 0.320 / 230 = 2.12% (≤ 3%, pass)

Use 8 AWG copper: 8/2 w/G UF-B (or 8 AWG THWN-2 in PVC) for the 120 ft trench to the control box, and 8/3 w/G submersible cable for the 200 ft well drop, with EGC upsized per NEC 250.122(B).

Example 2: 1/2 HP 115 V 2-wire pump, 60 ft trench + 100 ft well depth

A shallow-well 1/2 HP 115 V 2-wire pump (12.0 A SFA, 9.8 A NEC FLC) is 60 ft from the cabin panel at 100 ft depth (160 ft total) with a 3% voltage drop target.

Combined length = 60 ft + 100 ft = 160 ft NEC 430.22 ampacity = 12.0 A × 1.25 = 15.0 A (20 A 1-pole breaker) 10 AWG Cu drop = 2 × 12.0 × 1.24 × 0.160 / 115 = 4.14% (> 3%, fail) 8 AWG Cu drop = 2 × 12.0 × 0.778 × 0.160 / 115 = 2.60% (≤ 3%, pass)

Notice how 115 V requires twice the current and has half the voltage headroom of 230 V—forcing 8 AWG copper at just 160 ft, whereas the exact same 1/2 HP motor in 230 V (6.0 A SFA) runs 160 ft comfortably on 12 AWG copper (1.65% drop).

Example 3: 3 HP 230 V 3-wire deep well, 150 ft trench + 450 ft well depth

A 3 HP 230 V 3-wire submersible pump (17.0 A FLC/SFA) is set 450 ft deep with a 150 ft trench (600 ft total one-way run) and a 3% maximum voltage drop.

Combined length = 150 ft + 450 ft = 600 ft NEC 430.22 ampacity = 17.0 A × 1.25 = 21.3 A (30 A 2-pole breaker) 6 AWG Cu drop = 2 × 17.0 × 0.491 × 0.600 / 230 = 4.35% (> 3%) 4 AWG Cu drop = 2 × 17.0 × 0.308 × 0.600 / 230 = 2.73% (≤ 3%, pass)

600 ft combined run at 17.0 A requires 4 AWG copper conductors and a 30 A 2-pole breaker paired with a 3 HP 230 V control box. Under NEC 250.122(A) & (B), upsize the 10 AWG base EGC proportionally to 4 AWG copper (matching the 4 AWG circuit conductors).

Frequently asked questions

Why must submersible well pump wire sizing combine trench distance and well depth? The motor receives power through both the horizontal trench and the vertical borehole cable in series. Voltage drop happens across the total combined one-way length (trench + depth).
What is the difference between a 2-wire and a 3-wire submersible well pump? A 2-wire pump puts start components inside the motor (2 power wires + ground down the well, up to 1-1/2 HP). A 3-wire pump puts the capacitor and relay in an above-ground control box (3 power wires + ground down the well) and is standard/required for 2 HP through 5 HP motors.
Why is voltage drop limited to 3% on submersible well pumps? Submersible motors draw 4× to 6× starting inrush under water pressure. Staying within 3% running drop preserves starting torque and prevents nuisance thermal overload trips.

Related calculators and reference charts

Well pump Cu / OCPD —
No result View