Wire run cost & copper vs. aluminum comparison
Compare material cost, voltage drop, annual I²R energy loss, and payback time between copper and aluminum conductors.
Run, pricing and load
Enter distance, unit prices, and load to compare copper and aluminum.
- Total conductor length
- —
- Upfront material diff
- —
- Annual energy diff
- —
- Copper 25-yr total
- —
- Aluminum 25-yr total
- —
- 25-yr lifecycle winner
- —
Material, electrical loss, and lifecycle comparison
| Metric | Copper | Aluminum | Difference (Cu − Al) |
|---|
—
IEC mode uses $/m unit pricing and meters for conductor length, with IEC 60228 resistance adjusted to 75 °C and conservative AWG equivalents for NEC ampacity checks.
How wire cost, I²R energy loss, and payback interact
Comparing copper and aluminum conductors requires evaluating both upfront material cost and ongoing resistive heat losses (I²R) over the operating life of the circuit. While copper has lower resistivity per unit area, aluminum typically carries a 40% to 65% lower upfront purchase price even when stepped up one or two AWG/kcmil sizes for equivalent ampacity.
Total wire length = Distance × Conductors in run
Material cost = Total wire length × Unit price ($/ft or $/m)
Circuit power loss (W) = N_active × I² × (R_75C × Distance_kft)
[N_active = 2 for 1-phase/DC, 3 for balanced 3-phase; R_75C from NEC Ch. 9 Table 8]
Annual energy cost ($/yr) = (Loss_W / 1000) × Operating_hours × Electricity_rate
Simple payback (years) = Upfront_cost_premium / Annual_energy_savings
Total lifecycle cost (T) = Material_cost + (Annual_energy_cost × Years)
AL/CU or AL7CU/AL9CU (75 °C or 90 °C), torqued to manufacturer specifications, and treated with listed anti-oxidant compound when required by the equipment listing.
Three worked copper vs. aluminum cost comparisons
Example 1: 80 A subpanel feeder at 200 ft — 4 AWG Cu vs. 2 AWG Al
A 240 V 1-phase feeder carries 65 A for 2,500 hr/yr at $0.15/kWh over 200 ft (3 conductors = 600 ft total). 4 AWG Cu ($2.20/ft) is compared against equivalent-ampacity 2 AWG Al ($0.95/ft).
Copper (4 AWG, R = 0.308 Ω/kft):
Material = 600 × $2.20 = $1,320 | Drop = 3.34% | Loss = 520.5 W ($195.19/yr)
Aluminum (2 AWG, R = 0.319 Ω/kft):
Material = 600 × $0.95 = $570 | Drop = 3.46% | Loss = 539.1 W ($202.16/yr)
Upfront Al savings = $750 | Annual Cu energy advantage = $6.97/yr | Payback = 107.6 yr
Because 2 AWG aluminum has nearly the same resistance as 4 AWG copper, aluminum saves $750 upfront and remains $576 ahead even after 25 years of operation.
Example 2: Same-gauge comparison (conduit constrained) — 4 AWG Cu vs. 4 AWG Al
If an existing conduit limits the conductor size to 4 AWG and load is 60 A continuously (4,000 hr/yr at $0.20/kWh) over 150 ft (3 conductors = 450 ft):
Copper (4 AWG, R = 0.308 Ω/kft):
Material = 450 × $2.20 = $990 | Loss = 332.6 W (1,330.6 kWh/yr = $266.11/yr)
Aluminum (4 AWG, R = 0.508 Ω/kft):
Material = 450 × $0.75 = $337.50 | Loss = 548.6 W (2,194.6 kWh/yr = $438.91/yr)
Upfront Cu premium = $652.50 | Annual energy savings = $172.80/yr | Payback = 3.8 yr
At the same gauge under heavy continuous duty, copper’s lower resistance cuts wasted heat by 40% and pays back its material premium in 3.8 years.
Example 3: 200 A 3-phase commercial feeder at 300 ft — 3/0 AWG Cu vs. 250 kcmil Al
A 480 V 3-phase feeder carries 160 A for 3,000 hr/yr at $0.14/kWh over 300 ft (4 conductors = 1,200 ft total). 3/0 AWG Cu (200 A @ 75 °C, $7.80/ft) is compared against 250 kcmil Al (205 A @ 75 °C, $2.45/ft).
3/0 AWG Cu (R = 0.0766 Ω/kft): Material = $9,360 | Drop = 1.33% | Energy = $740.66/yr
250 kcmil Al (R = 0.0847 Ω/kft): Material = $2,940 | Drop = 1.47% | Energy = $818.98/yr
Upfront Al savings = $6,420 | Annual energy diff = $78.32/yr | Payback = 82.0 yr
Both choices remain well under the 3% feeder drop guideline; 250 kcmil aluminum saves $6,420 upfront and saves $4,462 net over 25 years.