Wire resistance, reactance and power loss
DC resistance, AC effective resistance, inductive reactance in PVC vs. steel conduit, circuit impedance, and annual energy cost from NEC Chapter 9 Tables 8 and 9.
Conductor and load parameters
Enter wire size, run length, and load current to calculate resistance and loss.
- DC resistance (Table 8)
- —
- AC resistance (Table 9)
- —
- Inductive reactance XL
- —
- Impedance |Z| / Z_eff
- —
- Annual energy loss
- —
- Annual energy cost
- —
PVC vs. aluminum vs. steel conduit comparison
Click any row to switch the active impedance model. Values include temperature correction and parallel sets.
| Model / Conduit | R (Ω/kft) | XL (Ω/kft) | |Z| (Ω/kft) | Z_eff (Ω/kft) | Run R (Ω) | Loss (W) | Energy (kWh/yr) | Cost ($/yr) |
|---|
—
In IEC mode, Table 8 DC calculations use IEC 60228 class 2 maximum resistance adjusted from 20 °C; Table 9 inductive reactance uses the nearest AWG conduit reactance.
Resistance, reactance, impedance, and power loss formulas
NEC Chapter 9 Table 8 provides conductor DC resistance at 75 °C, while Table 9 provides 60 Hz AC resistance (R_ac) and inductive reactance (X_L) for three single conductors in PVC, aluminum, and steel conduit. Temperature adjustment follows Chapter 9 Table 8 Note 2.
Temperature adjusted R: R_T = R_75 × [1 + α × (T − 75)] (α_Cu = 0.00323/°C, α_Al = 0.00330/°C)
Impedance magnitude: |Z| = √(R_ac² + X_L²)
Effective impedance: Z_eff = R_ac × PF + X_L × sin(arccos(PF))
Real power loss (W): P_loss = N_cond × I² × R_run (N_cond = 3 for 3-phase, 2 for 1-phase/DC)
Annual energy & cost: kWh/yr = (P_loss / 1000) × hours/yr | Cost = kWh/yr × $/kWh
Three worked wire resistance and energy loss examples
Example 1: 250 kcmil copper 200 A feeder at 250 ft, PVC vs. steel conduit
A 480 V 3-phase 200 A continuous industrial feeder runs 250 ft one-way at 75 °C and 0.85 power factor on 250 kcmil copper (operating 4,000 hr/yr at $0.15/kWh).
PVC conduit (Table 9): R_ac = 0.052 Ω/kft, X_L = 0.041 Ω/kft, Z_eff = 0.0658 Ω/kft
P_loss = 3 × 200² × (0.052 × 0.25) = 1,560 W (6,240 kWh/yr = $936/yr)
Steel conduit (Table 9): R_ac = 0.054 Ω/kft, X_L = 0.052 Ω/kft, Z_eff = 0.0733 Ω/kft
P_loss = 3 × 200² × (0.054 × 0.25) = 1,620 W (6,480 kWh/yr = $972/yr)
Switching from PVC to steel conduit raises effective voltage-drop impedance by 11.4% and adds 60 W of continuous eddy-current heat dissipation in the raceway.
Example 2: 12 AWG copper 20 A single-phase branch at 100 ft
A 120 V single-phase 20 A branch circuit runs 100 ft one-way (200 ft loop) on 12 AWG copper at 75 °C (R_dc = 1.98 Ω/kft, Table 9 R_ac = 2.0 Ω/kft).
Run DC resistance (1-way) = 1.98 × (100 / 1000) = 0.198 Ω
Loop DC resistance (2-wire) = 2 × 0.198 = 0.396 Ω
P_loss = 2 × 20² × 0.198 = 158.4 W (at 2,000 hr/yr: 316.8 kWh/yr = $47.52/yr)
At 12 AWG, skin effect is negligible, so Table 8 DC resistance and Table 9 AC resistance match within 1%.
Example 3: Temperature correction on 4/0 AWG aluminum at 90 °C
A 4/0 AWG aluminum feeder in PVC conduit operates near its 90 °C thermal limit (base Table 9 R_ac75 = 0.10 Ω/kft, X_L = 0.041 Ω/kft) at 0.90 power factor.
R_ac(90 °C) = 0.10 × [1 + 0.00330 × (90 − 75)] = 0.1050 Ω/kft (+5.0%)
|Z| = √(0.1050² + 0.041²) = 0.1127 Ω/kft
Z_eff = 0.1050 × 0.90 + 0.041 × sin(arccos(0.90)) = 0.1123 Ω/kft
Inductive reactance X_L stays constant with temperature because geometry does not change, while resistive heating R_ac increases by 5.0% from 75 °C to 90 °C.