NEC Table 310.16 ampacity table

Allowable ampacities of insulated conductors at 86 °F30 °C ambient and up to three current-carrying conductors. Click any row to open it in the ampacity calculator.

Table 310.16 conductor ampacities (A)

24 rows
Size Area Copper (A) Aluminum / CCA (A) 240.4(D)
OCPD
Open in calculator
60 °C 75 °C 90 °C 60 °C 75 °C 90 °C

Common branch-circuit and feeder sizes

Circuit rating Copper size 75 °C ampacity Typical application Open in calculator

Conditions of use and terminal limits

Base assumptions: Table 310.16 values apply to not more than three current-carrying conductors in a raceway, cable, or earth, at an ambient temperature of 86 °F (30 °C)30 °C (86 °F). When ambient temperature or conductor count differs, apply the temperature and bundling factors in NEC 310.15(B) and (C).
Termination rule (NEC 110.14(C)): Even when using 90 °C conductors such as THHN or XHHW-2, final ampacity is capped at the terminal temperature column: 60 °C or 75 °C for circuits 100 A or less (14 AWG through 1 AWG), and 75 °C for equipment over 100 A unless marked otherwise.
Small conductors (NEC 240.4(D)): Unless specifically permitted, overcurrent protection shall not exceed 15 A for 14 AWG Cu, 20 A for 12 AWG Cu (15 A Al), and 30 A for 10 AWG Cu (25 A Al), regardless of higher 75 °C or 90 °C column ampacities.
IEC conductor mapping: NEC ampacity tables cover AWG and kcmil sizes only. In IEC mode, each metric size uses the ampacity of the largest AWG or kcmil conductor whose cross-sectional area does not exceed the metric area.