Conduit and wire areas
NEC Chapter 9 Table 4 raceway fill limits and Table 5 insulated conductor areas. Click any conductor row to open it in the wire size calculator.
Chapter 9 Table 4 conduit dimensions and fill limits
| Conduit | Trade size (Metric) |
Internal dia (in) |
100% area (in²) |
1 wire 53% |
2 wires 31% |
3+ wires 40% |
Nipple 60% |
Max #12 THHN |
Open in calculator |
|---|
No rows match that filter. Try a trade size like “3/4”, “EMT” or a wire size like “12”.
Chapter 9 Table 5 insulated conductor dimensions
| Wire size | THHN / THWN-2 | XHHW / XHHW-2 | Open in calculator | ||
|---|---|---|---|---|---|
| Dia (in) | Area (in²) | Dia (in) | Area (in²) | ||
Chapter 9 Table 1 fill rules
Percent fill limits: Maximum raceway fill is 53% for 1 conductor, 31% for 2 conductors, and 40% for 3 or more conductors. For conduit nipples not exceeding 24 in600 mm between enclosures, Table 1 Note 4 permits up to 60% fill.
Mixed wire sizes: Add the Table 5 area of every insulated and bare conductor in the raceway (including equipment grounding conductors) and compare the sum against the Table 4 fill limit for the total conductor count.