Generator sizing and transfer switch inlet wire calculator
Sum running and starting surge watts with 20% headroom, recommend generator kW, and size L14-30 (30 A) vs. CS6365 (50 A) inlet box wire, breaker, and interlock kit.
Inlet and wiring parameters
Toggle appliances below to size your generator and transfer switch inlet.
- Total running watts
- —
- Peak starting surge
- —
- With 20% headroom
- —
- 240 V load / inlet
- —
- Total drop (cord + run)
- —
- Portable cord / EGC
- —
Interactive appliance running and surge watt calculator
0 active| Use | Appliance / circuit | Running (W) | Starting surge (W) | Qty | Subtotal (W) |
|---|
Transfer switch hardware, interlock notes, and take-off
| Component | Recommended specification | Code / notes |
|---|
Generator kW sizing, L14-30 vs. CS6365 inlets, and NEC interlock rules
Sizing a portable backup generator and transfer inlet requires balancing both continuous running wattage (with a 20% engine reserve) and momentary motor-starting surge wattage from compressors and pumps.
Total Running Watts = Σ (Running W × Qty)
Peak Surge Watts = Total Running W + max(Surge W - Running W)
Recommended Generator Running kW = (Total Running W × 1.20) / 1000
Inlet Current (240 V) = Total Running W / 240 V (≤ 30 A → L14-30, ≤ 50 A → CS6365)
L14-30 (30 A) vs. CS6365 / SS2-50 (50 A): A 30 A NEMA L14-30P inlet box supports up to 7,200 W (30 A × 240 V) and connects with 10/3 w/G NM-B (or 10 AWG THHN) on a 30 A 2-pole breaker. A 50 A CS6365 (twist-lock 4-wire) inlet box supports up to 12,000 W (50 A × 240 V) and requires 6/3 w/G NM-B indoors (since NEC 334.80 limits 8/3 NM-B to 40 A at 60 °C) or 8 AWG / 6 AWG Cu THHN in conduit on a 50 A 2-pole breaker.
Interlock kit & neutral bonding (NEC 702.5, 408.36(D), 250.30): A mechanical panel interlock must be UL-listed for your specific main panel and paired with a breaker hold-down retainer kit on the backfed generator breaker. Because standard interlocks and 2-pole transfer switches keep utility and generator neutrals bonded together in the main panel, you must configure a portable generator as a floating neutral (neutral-to-frame bond removed) unless using a 3-pole switched-neutral transfer switch.
Portable generator inlet & transfer wire reference (240 V 4-wire Cu)
| Inlet box | Breaker | Max 240 V W | NM-B Romex (60 °C) | THHN conduit (75 °C) | Portable cord | Cu EGC (250.122) |
|---|---|---|---|---|---|---|
| NEMA L14-20P | 20 A 2-pole | 4,800 W | 12/3 w/G NM-B | 12 AWG Cu THHN | 12/4 SOOW | 12 AWG Cu |
| NEMA L14-30P | 30 A 2-pole | 7,200 W | 10/3 w/G NM-B | 10 AWG Cu THHN | 10/4 SOOW | 10 AWG Cu |
| CS6365 / SS2-50P | 50 A 2-pole | 12,000 W | 6/3 w/G NM-B (55 A) | 8 AWG Cu (50 A) / 6 AWG Cu | 6/4 SOOW | 10 AWG Cu |
Three worked generator and inlet sizing examples
Example 1: Essential circuits backup with NEMA L14-30 (30 A) interlock
A homeowner backs up a refrigerator (700 W run / 2,200 W surge), sump pump (800 W / 2,000 W), gas furnace blower (800 W / 1,600 W), microwave (1,200 W), and lighting/Wi-Fi (600 W).
Total Running = 700 + 800 + 800 + 1,200 + 600 = 4,100 W (17.1 A @ 240 V)
With 20% headroom = 4,100 × 1.20 = 4,920 W → 5.0 kW running generator
Peak Surge = 4,100 + (2,200 - 700) = 5,600 W → 6.0 kW+ surge rating
Inlet & wiring: NEMA L14-30 (30 A, 7,200 W max), 30 A 2-pole breaker, 10/3 w/G NM-B, 10/4 SOOW cord
A 6,500 W / 8,000 W portable generator paired with a 30 A L14-30 inlet box, 10/3 w/G NM-B, and a listed panel interlock kit handles all essential loads with comfortable margin.
Example 2: Adding a 240 V well pump + central A/C forces CS6365 (50 A)
Adding a 1 HP submersible well pump (1,000 W / 2,800 W surge) and a 3-ton central A/C with soft-start or standard startup (3,500 W / 7,000 W surge) to the 4,100 W essential load.
Total Running = 4,100 + 1,000 + 3,500 = 8,600 W (35.8 A @ 240 V)
With 20% headroom = 8,600 × 1.20 = 10,320 W → 10.5 kW running generator
Peak Surge = 8,600 + (7,000 - 3,500) = 12,100 W → 12.5 kW+ surge rating
Inlet & wiring: CS6365 (50 A, 12,000 W max), 50 A 2-pole breaker, 6/3 w/G NM-B (or 6 AWG THHN), 6/4 SOOW
At 35.8 A (10.3 kW with headroom), a 30 A L14-30 inlet is overloaded—upgrade to a 50 A CS6365 inlet box, 50 A breaker with hold-down clip, and 6/3 w/G NM-B (remembering 8/3 NM-B is capped at 40 A under NEC 334.80).
Example 3: Long 100 ft exterior inlet run + 50 ft cord voltage drop check
A detached garage houses a 50 A CS6365 inlet 100 ft from the house main panel (wired in 75 °C THHN copper in PVC conduit) plus a 50 ft 6/4 SOOW portable cord at a 40 A continuous backup load.
Total conductor run = 100 ft (building) + 50 ft (cord) = 150 ft
On 8 AWG Cu (50 A @ 75 °C): 2 × 40 × 0.778 × 0.150 / 240 = 3.89% (> 3% rec.)
On 6 AWG Cu (65 A @ 75 °C): 2 × 40 × 0.491 × 0.150 / 240 = 2.46% (≤ 3%, pass!)
Pulling 6 AWG copper THHN (2 Hots + 1 Neutral + 10 AWG Cu EGC) in 3/4" conduit keeps combined cord and feeder voltage drop under 2.5%.