Equipment grounding (EGC) & GEC size calculator
NEC Table 250.122 EGC sizing with mandatory 250.122(B) proportional upsizing for voltage drop, plus NEC Table 250.66 GEC sizing.
Grounding parameters
Select overcurrent rating or service conductor size.
- Base Table 250.122
- —
- Upsize ratio (250.122(B))
- —
- Required EGC area
- —
- Copper EGC
- —
- Aluminum EGC
- —
- Installation rule
- —
NEC grounding table and calculation working
—
IEC mode converts NEC Table 250.122 and Table 250.66 wire sizes to the nearest IEC 60228 mm² cross-section; verify that the selected metric conductor meets or exceeds the required circular mil area.
NEC Article 250 grounding conductor sizing rules
Article 250 divides grounding conductors into two distinct roles: the Equipment Grounding Conductor (EGC) under NEC 250.122, which clears line-to-ground faults on branch circuits and feeders, and the Grounding Electrode Conductor (GEC) under NEC 250.66, which bonds the electrical service or separately derived system to earth electrodes.
Proportional EGC upsize (NEC 250.122(B)):
Area_EGC_required = Area_EGC_table × (Area_Phase_installed / Area_Phase_code_min)
Select smallest conductor in Ch. 9 Table 8 with cmil ≥ Area_EGC_required
Cap (NEC 250.122(A)): EGC need not exceed installed circuit conductors (same material)
Parallel service GEC (NEC 250.66):
Area_service_equiv = Area_single_service_conductor × Number_of_parallel_sets
Three worked EGC and GEC sizing examples
Example 1: 60 A feeder upsized from 6 AWG to 3 AWG Cu for voltage drop (NEC 250.122(B))
A 60 A feeder normally requires 6 AWG copper (26,240 cmil) and a 10 AWG copper EGC (10,380 cmil) from Table 250.122. Because of a long 200 ft run, the phase conductors are upsized to 3 AWG copper (52,620 cmil).
Base EGC (60 A OCPD) = 10 AWG Cu (10,380 cmil)
Upsize ratio = 52,620 / 26,240 = 2.005×
Required EGC = 10,380 × 2.005 = 20,816 cmil
Next standard size ≥ 20,816 cmil = 6 AWG Cu (26,240 cmil)
8 AWG copper (16,510 cmil) is too small to reach 20,816 cmil, so NEC 250.122(B) mandates stepping up two EGC sizes to 6 AWG copper.
Example 2: Parallel 400 A feeder in two conduits with upsized phase wire (NEC 250.122(F))
A 400 A breaker feeds two parallel conduits. Code minimum for 200 A per set is 3/0 AWG Cu (167,800 cmil), upsized to 250 kcmil Cu (250,000 cmil) for voltage drop.
Base Table 250.122 EGC (400 A OCPD) = 3 AWG Cu (52,620 cmil)
Upsize ratio = 250,000 / 167,800 = 1.490×
Required EGC = 52,620 × 1.490 = 78,397 cmil → 1 AWG Cu (83,690 cmil)
NEC 250.122(F): Install one 1 AWG Cu EGC in EACH of the 2 raceways
Under NEC 250.122(F), you cannot split or halve the EGC across parallel conduits; each raceway carries a full 1 AWG copper EGC.
Example 3: 400 A service with parallel 4/0 AWG aluminum conductors (NEC Table 250.66)
A 400 A residential/commercial service uses two parallel sets of 4/0 AWG aluminum service-entrance conductors (211,600 cmil each) per phase, bonded to structural steel and a pair of ground rods.
Equivalent service area = 211,600 × 2 = 423,200 cmil (Aluminum)
Table 250.66 row: Over 250 through 500 kcmil Al → 2 AWG Cu (or 1/0 Al)
GEC to building steel / water pipe = 2 AWG Cu
Sole GEC to ground rods (250.66(A)) = 6 AWG Cu
Even though the full Table 250.66 GEC is 2 AWG copper, the separate branch running solely to driven ground rods does not need to exceed 6 AWG copper under NEC 250.66(A).