Watts, volts, amps, kVA and HP converter
Bidirectional conversion across Watts, kW, kVA, Volts, Amps, and Horsepower for DC, 1-phase AC, and 3-phase AC with PF and efficiency.
Electrical quantities
Enter voltage and any power or current quantity to convert across all units.
- Line current
- —
- Real power (P)
- —
- Apparent power (S)
- —
- Reactive power (Q)
- —
- Shaft output (HP)
- —
- Next std OCPD (240.6)
- —
Same power across standard NEC voltages
Click any voltage row to apply it. Wire sizes assume 75 °C copper terminals, 30 °C ambient, and 100% non-continuous duty.
| System voltage | Current (A) | 125% cont. (A) | Next OCPD | Min Cu wire (75 °C) | Load impedance |
|---|
—
IEC mode shows conservative AWG equivalents mapped to metric mm² from NEC Table 310.16; power formulas are identical in SI and US units.
Electrical power equations for DC, 1-phase, and 3-phase
Electrical power conversion links line voltage (V), line current (I), power factor (PF), and phase configuration (K = 1 for DC or 1-phase AC, K = √3 ≈ 1.732 for balanced 3-phase AC). Motor efficiency (η) relates electrical input watts to mechanical shaft horsepower (1 HP = 745.7 W).
DC (PF = 1):
P_W = V × I | I = P_W / V | V = P_W / I | kVA = kW
1-Phase AC:
S_kVA = (V × I) / 1000 | P_kW = S_kVA × PF | Q_kVAR = √(S_kVA² - P_kW²)
I = (P_kW × 1000) / (V × PF) | V = (P_kW × 1000) / (I × PF)
3-Phase AC:
S_kVA = (√3 × V_LL × I) / 1000 | P_kW = S_kVA × PF
I = (P_kW × 1000) / (√3 × V_LL × PF) | V_LL = (P_kW × 1000) / (√3 × I × PF)
Mechanical Horsepower (1 HP = 745.7 W):
HP = (P_W × η) / 745.7 | P_W = (HP × 745.7) / η
Three worked power conversion examples
Example 1: 10 HP 3-phase 480 V motor at 0.85 PF and 90% efficiency
Convert a 10 HP mechanical load on a 480 V 3-phase feeder with 90% motor efficiency and 0.85 lagging power factor into electrical kW, kVA, and line current.
Shaft output = 10 HP × 745.7 W/HP = 7,457 W (7.46 kW_mech)
Input real power = 7,457 W / 0.90 = 8,285.6 W (8.29 kW_elec)
Apparent power = 8.286 kW / 0.85 PF = 9.75 kVA | Reactive = 5.13 kVAR
Line current = 8,285.6 / (480 × √3 × 0.85) = 11.72 A
The motor draws 11.72 A line current and 9.75 kVA of transformer capacity while delivering 10 HP at the shaft.
Example 2: 9.6 kW load at 240 V 1-phase vs. 208 V 1-phase (PF = 1.00)
Compare line current for a 9,600 W resistive EVSE or water heater supplied at 240 V residential vs. 208 V commercial single-phase.
At 240 V 1-ph: I = 9,600 W / (240 V × 1.00) = 40.0 A (50 A cont. OCPD)
At 208 V 1-ph: I = 9,600 W / (208 V × 1.00) = 46.15 A (60 A cont. OCPD)
Dropping from 240 V to 208 V increases current by 15.4% for the same kW, pushing a continuous 9.6 kW load from a 50 A circuit into a 60 A circuit.
Example 3: Bidirectional voltage solve — 15 kVA 3-phase load at 36.1 A
A balanced 3-phase machine draws 36.1 A at 15.0 kVA apparent power (0.80 PF = 12.0 kW). Switch mode to Solve Volts to identify the supply voltage.
V_LL = (15.0 kVA × 1000) / (√3 × 36.1 A) = 239.9 V → 240 V 3-phase
Real power = 15.0 × 0.80 = 12.0 kW | Reactive power = 9.0 kVAR
Solving voltage from kVA and Amps confirms a 240 V three-phase supply without needing to know PF in advance (since S = √3 × V × I).