Electric motor wire and breaker calculator
Lookup NEC Table 430.248 (1-phase) and Table 430.250 (3-phase) FLC from 1/2 HP to 200 HP, size 125% conductors (430.22), and inverse-time breakers up to 250% (430.52).
Motor and circuit parameters
Select motor horsepower, voltage, and run length to compute conductor and OCPD sizes.
- NEC Table FLC
- —
- Min wire ampacity (125%)
- —
- Max branch OCPD (430.52)
- —
- Max overload relay (430.32)
- —
- Running voltage drop
- —
- EGC / Min conduit
- —
NEC 430.52 protective device limits & bill of materials
NEC 240.4(G) motor circuit rule: Motor branch-circuit conductors are sized at 125% of Table FLC (NEC 430.22) and protected from overloads by the motor starter/overload relay (NEC 430.32). The general small-conductor caps in 240.4(D) do not restrict the branch-circuit breaker or fuse selected under Table 430.52.
| NEC Table 430.52 device | Max % FLC | Calculated | Max std rating | EGC (250.122) |
|---|
| Component | Specification | Code basis |
|---|
IEC mode selects the smallest metric cross-section whose conservative AWG equivalent satisfies the NEC 430.22 125% FLC ampacity and computes voltage drop using IEC 60228 resistance.
NEC Article 430 motor branch-circuit sizing method
Sizing an electric motor branch circuit separates thermal overload protection from high-inrush short-circuit protection. All conductor and breaker limits start from the NEC Table Full-Load Current (FLC), not the motor nameplate current.
1. Lookup Table FLC: NEC Table 430.248 (1-phase) or Table 430.250 (3-phase)
2. Branch conductors (NEC 430.22): I_cond_min = 1.25 × FLC (checked at 75 °C terminals & 90 °C derated)
3. Branch OCPD max (NEC 430.52):
Inverse-time breaker = 250% × FLC (round up to next std 240.6(A) size per Exc. 1)
Dual-element fuse = 175% × FLC | Non-time-delay fuse = 300% × FLC | MCP = 800% × FLC
4. Overload relay max (NEC 430.32): 125% × Nameplate FLA (SF ≥ 1.15 or ≤ 40 °C), else 115% × FLA
110.14(C) termination rule: Motors rated over 100 A or circuits over 100 A use the 75 °C ampacity column in NEC Table 310.16. Even when using 90 °C THHN conductors, ambient temperature correction and bundling derating start from the 90 °C column, while final conductor termination ampacity cannot exceed the 75 °C (or 60 °C for ≤ 100 A equipment with 60 °C lugs) column.
NEC Table 430.250 full-load current reference (3-phase)
Three worked motor circuit examples
Example 1: 5 HP, 230 V, 1-phase shop air compressor (75 ft)
A 5 HP single-phase 230 V motor has a nameplate FLA of 26.0 A (SF 1.15) and is fed 75 ft in 3/4" EMT with 90 °C copper THHN on 75 °C terminals.
NEC Table 430.248 FLC (5 HP, 230 V, 1-phase) = 28.0 A
NEC 430.22 min conductor ampacity = 1.25 × 28.0 A = 35.0 A → 10 AWG Cu (35 A at 75 °C)
NEC 430.52 inverse-time breaker max = 2.50 × 28.0 A = 70 A (exact standard rating)
NEC 430.32 overload max = 1.25 × 26.0 A nameplate = 32.5 A
Voltage drop (10 AWG Cu, 75 ft): 2 × 28 × 1.24 × 0.075 / 230 = 2.26% (≤ 3%, pass)
10 AWG copper with an 8 AWG copper EGC (sized from the 70 A breaker per Table 250.122) in 1/2" EMT satisfies all NEC Article 430 requirements. Note that 10 AWG is allowed on a 70 A motor breaker under NEC 240.4(G).
Example 2: 10 HP, 460 V, 3-phase industrial lathe (75 ft)
A 10 HP, 460 V, 3-phase induction motor runs 75 ft in EMT using 75 °C copper terminals at 86 °F (30 °C) ambient.
NEC Table 430.250 FLC (10 HP, 460 V, 3-phase) = 14.0 A
NEC 430.22 min conductor ampacity = 1.25 × 14.0 A = 17.5 A → 14 AWG Cu (20 A at 75 °C)
NEC 430.52 inverse-time breaker max = 2.50 × 14.0 A = 35 A (or 1.75 × 14 = 24.5 → 25 A dual-element fuse)
Voltage drop (14 AWG Cu, 75 ft): √3 × 14 × 3.14 × 0.075 / 460 = 1.24% (≤ 3%, pass)
14 AWG copper with a 35 A 3-pole inverse-time breaker and 10 AWG copper EGC (Table 250.122 for 35 A) in 1/2" EMT is code-compliant. Many industrial plants specify 12 AWG minimum for mechanical robustness.
Example 3: 50 HP, 208 V, 3-phase chiller pump (180 ft run, 3/0 AWG Cu)
A 50 HP, 208 V, 3-phase pump sits 180 ft from the motor control center in 86 °F (30 °C) ambient with a 3% running voltage drop target.
NEC Table 430.250 FLC (50 HP, 208 V, 3-phase) = 143 A
NEC 430.22 min conductor ampacity = 1.25 × 143 A = 178.8 A → 3/0 AWG Cu (200 A at 75 °C)
Voltage drop at 3/0 Cu (180 ft, Table 9 Z_eff @ 0.85 PF): 1.89% in PVC (0.088 Ω/kft) | 2.02% in steel EMT (0.095 Ω/kft)
NEC 430.52 inverse-time breaker max = 2.50 × 143 A = 357.5 A → 400 A breaker (Exception 1 next standard)
3/0 AWG copper satisfies both the 178.8 A ampacity requirement and keeps running voltage drop at 1.89% in PVC (2.02% in steel EMT, both well under 3%), protected by up to a 400 A inverse-time breaker and a 3 AWG copper EGC in 2" EMT.